UTILITY PACKAGE (GX Configurator-DA)

5.6.4 Pass data

5 - 25
Perform operation in the following sequence to save/restore the user range.
(1) Switch to the pass data screen
Perform the operation in Section 5.6.1 to display the Pass data screen.
(2) User range saving
(a)
Set the user range to be used in the Setting value field of CH
classification setting, and click the
When the user range setting is completed, the set user range is displayed in
the Current value field of CH
(b)
Change the Setting value field of Pass data read request to "Request", and
click the
Execute test
When read is completed, the values are displayed in the Current value fields
of CH
Industrial shipment settings offset/gain values/CH
settings offset/gain values.
(c)
Compare the values with those in the range reference table, and record
them if they are correct.
Refer to Section 7.4 for the range reference table.
Execute test
Pass data classification setting.
button.
MELSEC-Q
Pass data
button.
User range
5 - 25