7.3.3 When user range setting is used and initial setting was made with GX Configurator-DA
(other system is available)
7 - 13
(1) Conversion disable
(a)
Take the following steps to disable the conversion:
1)
Set D/A conversion enable/disable setting (buffer memory address 0:
Un\G0) to All channel conversion disable (3
2)
Turn Operating condition setting request (Y9) from off to on to stop the
conversion.
3)
Operating condition setting completed flag (X9) turns off from on.
4)
Check that the conversion is stopped by seeing the actual analog
output value.
5)
Turn Operating condition setting request (Y9) from on to off.
(2) Dismounting of module
(a)
After choosing [Diagnosis] - [Online module change] on GX Developer to
enter the "Online module change" mode, double-click the module to be
changed online to display the "Online module change" screen.