Display and control panel AMS 348i
Position value submenu
Notice!
The parameters mentioned in the "Position value", "I/O" and "Other" sub-menus must be
set via the GSDML file of the AMS 348i. For test purposes, the parameters can be changed
directly on the AMS
parameter enable, however, the parameters stored in the GSDML file continue to be valid.
The parameters changed directly on the AMS
Table 8.3:
Level 3
Measurement
unit
Count direction
Offset
Preset
Free resolution 
value
Error delay
Position value in
the case of error
45
348i
via the display structure described below. After deactivation of the
Position value submenu
Level 4
Level 5
Selection/configuration option
Description
Metric/Inch
Specifies the units of the measured distances
Positive/Negative
Positive: The measurement value begins at 0 and increases with
increasing distance.
Negative: The measurement value begins at 0 and decreases with
increasing distance. Negative distance values may need to be
compensated with an offset or preset.
Output value=measurement value+offset.
The resolution of the offset value is independent of the selected
"Resolution position" and is entered in mm or inch/100. The offset value
is effective immediately following entry. If the preset value is activated,
this has priority over the offset. Preset and offset are not offset against
each other.
The preset value is accepted by means of teach pulse. The teach pulse
can be applied to a hardware input of the M 12 PWR connector. The
hardware input must be appropriately configured. See also configuration
of the I/Os.
The measurement value can be resolved in increments of 1/1000 within
the 5 ... 50000 value range. If, e.g., a resolution of 0.875 mm per digit
is required, the parameter is set to 875.
ON / OFF
Specifies whether, in the event of an error, the position value immediately
outputs the value of the "Position value in the case of error" parameter
or the last valid position value for the configured error delay time.
Last valid value / zero
Specifies which position value is output after the error delay time elapses.
348i
for test purposes are overwritten again.
AMS
348i
Standard
Metric
Positive
0 mm
0 mm
1000
ON/100 ms
Null