3.2 Wiring Precautions
This section describes the procedures and precautions for wiring power cords.
3.2.1
Connecting the Power Cord
To avoid an electric shock, prior to connecting the PS-G unit's power cord terminals to the
power terminal block, confirm that the PS-G unit's power supply is completely turned OFF,
via a breaker, or similar unit.
The PS3600G-T41 units are designed to use AC100 to 240V input. The PS3600G-T41-
24V is designed to use only DC24V. Supplying a power voltage other than that specified
will damage the power source and the PS-G unit.
When the FG terminal is connected, be sure the wire is grounded.
When wiring the PS3600G-T41 unit (AC100 to 240V)
Double-insulated Wire
Power Cord
1.25 to 2.0mm
(16 to 14 AWG)
V2-MS3 compatible
(J.S.T. Mfg. Co., Ltd)
Recommended
*1
Ring Terminal
*1 In order to prevent a short circuit caused by loose screws, make sure to use a crimp-type terminal with insulating
sleeve.
• When the FG terminal is connected, be sure the wire is grounded. Not grounding
the PS-G unit will result in excess noise and vibration.
• The SG and FG terminals are connected internally in the PS-G unit.
• When connecting the SG wire to another device, be sure that the design of the
system/connection does not produce a shorting loop.
AC Power Cord
2
[0.0024 to 0.0062inch
3.2mm [0.13 in.]
or more
less than
6mm [0.24 in.]
Chapter 3 Hardware Installation
Grounding Wire
2
1.25 to 2.0mm
[0.0024 to 0.0062inch
2
]
(16 to 14 AWG)
V2-P4 compatible
(J.S.T. Mfg. Co., Ltd)
less than
7mm [0.28 in.]
2
]
4.3mm [0.17 in.]
or more
3-7