• Be sure that the ambient operation temperature and the ambient humidity are within
their designated ranges. (Ambient operation temperature: 0 to 50°C, Ambient
humidity: 10 to 90%RH, Wet bulb temperature: 39°C max.) When installing
the PS-G on the panel of a cabinet or enclosure, "Ambient operation temperature"
indicates both the panel face and cabinet or enclosure's internal temperature.
• Be sure that heat from surrounding equipment does not cause the PS-G to exceed
its standard operating temperature.
• When installing the PS-G in a slanted panel, the panel face should not incline more
than 30°.
• When installing the PS-G in a slanted panel, and the panel face inclines more than
30°, the ambient temperature must not exceed 40°C. You may need to use forced
air cooling (fan, A/C) to ensure the ambient operating temperature is 40°C or below.
• The PS-G Series unit does not support longitudinal mounting.
Cabinet
Panel
interior
face
30° or less