Ultrastar Serv60+8 Rack Requirements - Western Digital Ultrastar Serv60+8 User Manual

Hide thumbs Also See for Ultrastar Serv60+8:
Table of Contents

Advertisement

User Guide
Figure 13: SSD Assembly LED
Table 11: SSD LED Identification
LED Name
Drive Multi-function LED Amber
1.8   Ultrastar Serv60+8 Rack Requirements
The Ultrastar Serv60+8 is designed to be installed into a rack that meets the EIA-310 standard at a minimum
1200 mm (47.24in.) of usable rack space, frame to frame. The vertical rack rails must be set between
812.8mm - 914.4mm / 32 in. - 36 in. to support the enclosure. It requires 4U of rack space, and it should be
installed into the rack at the lowest possible U height to keep the load on the rack balanced.
Table 12: Required Rack Specifications
Parameter
Vertical Rack Rail Spacing
Static Load Rating
Dynamic Load Rating
Color
Rack Depth
1200 mm (47.24in.) of usable rack space, frame to frame
450mm (17.72in.) minimum width with 465mm (18.31in.) ± 1.5mm nominal
Rack Width
hole spacing and W1 is 492mm minimum. See EIA-310 Rack Standard
Rack Units (U)

1.8 Ultrastar Serv60+8 Rack Requirements

Solid – Drive identify
Blink @ 1 Hz (50% duty cycle) – Drive fault
Off – Drive has no faults
Requirement
4U
812.8mm - 914.4mm / 32 in. - 36 in.
1360.7 kg. / 3000 lbs.
1020.5 kg. / 2250 lbs.