UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Figure 3-34 Neutral wire
When connecting the battery cables, wrap cables with corrugated pipes for protection, and
reinstall the removed insulation panels at the rear of the cabinet.
----End

3.2.5 Routing at the Bottom

Context
Procedure
Step 1 Remove the cover plate from the cable hole at the bottom of the tail frame.
Step 2 Remove the insulation panels at the rear of the cabinet.
Step 3 Connect a ground cable to the safety ground of the UPS cabinet.
Issue 09 (2019-12-20)
Cables can be routed in and out from the bottom only when a tail frame is configured for
the cabinet.
This section uses the 02311FTE-004 cabinet as an example. For details about cable
connections in other cabinets, see the procedure in this section.