Huawei UPS5000-E Series User Manual page 134

Integrated ups, 50/125 kva
Hide thumbs Also See for UPS5000-E Series:
Table of Contents

Advertisement

UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Bypass Parameter Settings
Figure 4-43 Bypass Parameter screen
Battery Parameter Settings
Issue 09 (2019-12-20)
Bypass frequency range (Hz)
When the difference between the bypass input frequency and the rated frequency is
greater than this value, the system determines that the bypass frequency is abnormal and
that the bypass is unavailable.
The bypass frequency range must be greater than the ECO frequency range. The value
range is ± 0.5 Hz to ± 6 Hz, and the default value is ± 2 Hz.
Maximum bypass voltage
Upper threshold for the bypass voltage. When the difference between the bypass voltage
and the rated voltage exceeds this value, the system determines that the bypass voltage is
abnormal and that the bypass is unavailable.
When the voltage level is 380 V, the value range is 10%, 15% (default), 20%, and 25%.
When the voltage level is 400 V, the value range is 10%, 15% (default), and 20%.
When the voltage level is 415 V, the value range is 10% (default) and 15%.
Minimum bypass voltage
Lower threshold for the bypass voltage. When the difference between the bypass voltage
and the rated voltage exceeds this value, the system determines that the bypass voltage is
abnormal and that the bypass is unavailable. The value can be –10%, –15%, –20%
(default), –30%, –40%, –50%, or –60%.
ECO voltage range
In ECO mode, when the difference between the bypass voltage and the rated voltage is
greater than this value, the system determines that the ECO voltage is abnormal and
transfers to normal mode. The values can be ± 5% (default), ± 6%, ± 7%, ± 8%, ± 9%, or
± 10%.
BPM mode upon BPM overtemp.
This parameter specifies whether to start bypass mode if overtemperature occurs.
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
125

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents