Battery parameter settings have great impact on battery maintenance, battery lifespan, and
UPS discharge time. When you set battery parameters, note the following:
Retain default settings for Chg. cur. limiting coef. and Cell float voltage. Only
professional maintenance personnel are allowed to change the settings.
When you set parameters, ensure the following: Chg. cur. limiting coef. >
Transfer-to-equalized charging cur. Coef; Dis. cur. 0.1C EOD ≥ Dis. cur. 0.3C EOD ≥
Dis. cur. 0.5C EOD ≥ Dis. cur. 1.0C EOD.
Battery type must meet the actual situation. Currently, only VRLA batt. is supported.
Chg. volt. over range point and Dis. volt. over range point are used to check whether
the batteries in each battery string have the same charge voltage and discharge voltage.
When a value exceeds the specified range, an alarm is generated. The calculation formula
is (Charge/Discharge voltage - Average voltage)/Average voltage x 100%. The
charge/discharge voltage and average voltage are obtained from the BMU. If the BMU is
not configured, you do not need to set these two parameters.