Huawei UPS5000-E Series Quick Manual

Hide thumbs Also See for UPS5000-E Series:

Advertisement

Quick Links

UPS5000-E-(400 kVA-600 kVA)
Quick Guide (60 kVA Power Modules)
Issue: 04
Part Number: 31509985
Date: 2019-12-24
1
Overview
Model
UPS5000-E-400K-FMS
Weight (full
680 kg
configuration)
Dimensions (H
2000 mm x 1200 mm x 850 mm
x W x D)
1. Before installation, read the user manual carefully to get familiar with product information and
safety precautions.
2. Use insulated tools during installation and operation.
3. Only engineers certified by Huawei or its agents are allowed to install, commission, and maintain
the UPS. Otherwise, personal injury or equipment damage may occur, and the UPS faults
caused are beyond the warranty scope of Huawei.
UPS5000-E-400K-FMS
(1) Power modules
(5) Bypass module
(2) Control module
(6) Main input switch
Copyright © Huawei Technologies Co., Ltd. 2019. All rights reserved.
UPS5000-E-500K-FMS
800 kg
UPS5000-E-500K-FMS
(3) Power distribution
module covers
(7) Output switch
1
UPS5000-E-600K-FMS
1025 kg
2000 mm x 1400 mm x
850 mm
(4) Maintenance bypass
switch
(8) Bypass input switch

Advertisement

Table of Contents
loading

Summary of Contents for Huawei UPS5000-E Series

  • Page 1 2. Use insulated tools during installation and operation. 3. Only engineers certified by Huawei or its agents are allowed to install, commission, and maintain the UPS. Otherwise, personal injury or equipment damage may occur, and the UPS faults caused are beyond the warranty scope of Huawei.
  • Page 2: Installing The Ups

    UPS5000-E-600K-FMS (1) Power modules (2) Control module (3) Power distribution module covers (4) Maintenance bypass switch (5) Bypass module (6) Main input switch (7) Output switch (8) Bypass input switch UPS5000-E-400K-SMS, UPS5000-E-500K-SMS, and UPS5000-E-600K-F600-SMS are models in standard configuration. A UPS in standard configuration has no mains input switch, bypass input switch, or output switch.
  • Page 3 A: Mounting holes on the channel steel B: Mounting holes on the floor 400/500K Hole dimensions Unit: mm 600K Hole dimensions Unit: mm...
  • Page 4: Installing Cables

    Securing the UPS • Ground mounting: Secure the cabinet to the ground by using eight M12x60 expansion bolts. • Steel channel mounting: Secure the cabinet to steel channels by using eight M12x60 common bolts. (1) Cabinet mounting holes (ground installation mode) (2) Cabinet mounting holes (channel steel installation mode) Installing the Front, Rear, Left, and Right Anchor Baffle Plates Installing Cables...
  • Page 5 The cabling route is for reference only. Connect cables based on site requirements. Installing Cables Scenario 1: Routing Cables from the Top 2. Remove the top cover from the cabinet 1. Open the front door of the bypass cabinet, based on cable routes and dimensions. and remove power distribution covers (UPS5000-E-400K-FMS is used as an example).
  • Page 6 3. Remove the copper bar between the mains 4. Connect the ground cable to the UPS. and bypass inputs. (Skip this step if there is only one mains input) 5. Connect the mains input power cable. 6. Connect the output power cable.
  • Page 7 8. Connect the battery cable. 7. Connect the bypass input power cable. 9. Connect signal cables. Route a neutral wire from the middle of the positive and negative battery strings. Take a battery string consisting of 40 batteries as an example. A neutral wire is routed from the middle of positive and negative battery strings, each consisting of 20 batteries.
  • Page 8: Verifying The Installation

    Scenario 2: Routing Cables from the Bottom 1. Remove the cable covers from the bottom of the cabinet, drill holes in the covers, attach grommet strips to the hole edges for protecting cables, and reinstall the cable covers. 2. Connect power cables and signal cables. For the screw specifications and torque used for connecting cables in a bottom cable routing scenario, refer to the top cable routing scenario.
  • Page 9: Powering On And Starting The Ups

    2. (Remove the paper protective film from the sealing putty.) After routing cables and verifying cable connections, seal the gap between cables and the cabinet using sealing putty. Paper protective film Sealing putty Sealing putty must be used as a whole and the gap can be sealed only from the top. 3.
  • Page 10: Powering On The Ups

    (For a UPS in full configuration ) Close the UPS bypass input switch, output switch, and mains input switch. After the UPS is powered on, initialization begins. The MDU displays the Huawei logo and an initialization progress bar. Starting the Inverter...
  • Page 11 b. After you set parameters on the Settings Wizard screen, the MDU displays the Bypass mode and No battery alarms, which do not need to be handled. If there is any other alarm, you need to rectify the fault. c. View the system running diagram on the MDU to check that the UPS is working in bypass mode. •...
  • Page 12: Shutting Down The Ups

    Powering On Loads 1. After the inverter starts, the UPS works in normal mode. The Bypass mode alarm disappears. 2. After confirming that the battery strings are properly connected, turn on the battery string input circuit breaker. If there are multiple battery strings, turn on the circuit breaker for each battery string and then the general circuit breaker between battery strings and the UPS.
  • Page 13 Scan here for technical support (carrier): Huawei App Store Scan here for more documents: Support-E Support WeChat You can also log in to Huawei technical support website: http://support.huawei.com/enterprise http://support.huawei.com Huawei Technologies Co., Ltd. Huawei Industrial Base, Bantian, Longgang Shenzhen 518129 People's Republic of China...

This manual is also suitable for:

Ups5000-e-400k-fmsUps5000-e-500k-fmsUps5000-e-600k-fms