UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Figure 3-30 Input terminals
----End
3.2.4.4 Connecting AC Output Power Cables
Connect AC output power cables to the UPS from inside out and from top to bottom. Connect
the PE cable, N cable, and L cable in sequence.
The method for connecting AC output power cables is the same for the 50 kVA, and 125 kVA
cabinets. The AC output power cable connection for the UPS5000-E-125K-HASBS cabinet is
used as an example.
Connect output power cables to the customer terminal bars in the UPS cabinet, and connect N
cables and PE cables to the N bar and PE bar on the left and right sides.
Issue 09 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
3 Installation
82