Huawei UPS5000-E Series User Manual page 171

Integrated ups, 50/125 kva
Hide thumbs Also See for UPS5000-E Series:
Table of Contents

Advertisement

UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Figure 5-1 Settings Wizard screen
Table 5-5 Settings Wizard parameters
Menu
Language
Time
Network
Param.
System Param.
1
System Param.
2
Issue 09 (2019-12-20)
Parameter
Setting
N/A
Select based on actual conditions.
Date format
Select based on actual conditions.
YYYY-MM-D
Actual date
D
Time zone
Actual time zone
Time
Actual time
IP address
Automatic (DHCP)
allocation
IP address
After IP address allocation is set to Automatic, IP
address, subnet mask, and gateway will be assigned by
Subnet mask
the DHCP server (ECC800).
Gateway
Single/Parallel
Single
Output voltage
Output voltage level refers to line voltage and should
level (V)
be set based on actual conditions.
Output
Set based on actual conditions.
frequency (Hz)
Battery capacity
Battery capacity = Battery capacity of a battery string
(Ah)
x Number of battery strings connected in parallel (For
example, if the battery capacity of a battery string is
150 Ah and two battery strings are connected in
parallel to the UPS, set the battery capacity to 300
Ah.)
Number of cells
Indicates the number of 2 V batteries in a battery
string connected to the UPS.
Copyright © Huawei Technologies Co., Ltd.
5 Operations
162