Figure 5-11 Logging in to the WebUI
Step 5 On the home page of the WebUI, choose Monitoring > Control, click Inv. ON, and confirm
the operation to start the inverter.
Figure 5-12 Starting the inverter
----End

5.3.3 Powering On Loads

After the inverter starts, the UPS works in normal mode. The Bypass mode alarm disappears.
Check that the UPS has transferred to normal mode by viewing the system running status
diagram.
Issue 09 (2019-12-20)
If the power module receives a startup command when it cannot be started, the startup command will be
kept for 1 minute. If the startup command is not cleared within 1 minute (for example, other faults occur
on the module, or you perform shutdown or rectify faults) and the module can be started, the module
responds to the startup command.