UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Alarm ID
Alarm Name
(Alarm
ID-Cause
ID)
0032-1
Battery overvoltage
protection
0036-2
Battery
maintenance
reminder
0037-1
Battery
undervoltage
0040-7
Rectifier abnormal
Issue 09 (2019-12-20)
Severity
Cause
monitoring cable
is faulty.
The dry contact
board is faulty.
Critical
The battery
voltage is greater
than the upper
threshold.
The configured
number of
batteries is less
than the actual
number.
The actual
number of
batteries does not
meet
requirements.
Warning
The time for
maintenance arrives.
Critical
The UPS has
worked in battery
mode for an
extended amount
of time.
The charger is
faulty.
Critical
The fan for the
power module is
not functioning
properly.
The air channel
for the power
module is
Copyright © Huawei Technologies Co., Ltd.
C Alarm List
Solution
faulty by replacing it with a
new one.
3. If no battery grounding failure
detector is available, check on
the dry contact board whether
the battery grounding failure
detector is enabled. If yes,
disable it and check whether
the alarm is cleared. If the
alarm persists, the dry contact
board may be faulty. Replace
the board.
1. Check the battery voltage.
2. Check that the configured
number of batteries matches
the actual number.
3. Check that the actual number
of batteries meets
requirements.
Maintain the batteries.
1. Check whether the battery
voltage is normal.
2. Check whether the output is
overloaded.
3. Check whether any battery is
damaged. If yes, replace the
battery.
4. Check whether any battery
charger generates an alarm. If
yes, replace the faulty module.
1. Check that the air channel for
the module is free from
blockage.
2. Check whether the fans are
functioning properly. Replace
the power module if the fans
are faulty.
236