User Manual (60 kVA, PF=0.9)

3.2.5.2 Bottom Cable Routing

Context
● There must be sufficient space at the bottom of the cabinet for bottom cable
● If cables need to be routed through holes, remove cable covers for power
● This section describes cable connections when the mains input and bypass
● Determine the cable cross-sectional area and quantity based on the section
Procedure
Step 1 Open the front door of the cabinet, and remove the front covers of the PDU from
the bypass cabinet.
Step 2 Remove the cable covers from the bottom of the cabinet, drill holes in the covers,
attach grommet strips to the hole edges to protect cables, and reinstall the cable
covers.
The hole size and quantity are for reference only.
Issue 06 (2022-01-27)
NO TICE
routing.
cables from the bypass cabinet and drill holes in the covers. After drilling holes,
attach grommet strips on the hole edges to protect cables. Reinstall the covers
on the cabinet.
input use different power sources. When they use the same power source, there
is no need to remove the copper bars between the mains and bypass input
terminals or connect the bypass input power cables.
"Preparing Power Cables" and site requirements. The figures are for reference
only.
NO TE