Figure 4-39 Advanced Param. screen 3
Figure 4-40 Advanced Param. screen 4
Issue 09 (2019-12-20)
System capacity (kVA)
Rated system capacity, equals to capacity of each power module multiplied by the
number of requisite power modules. The Module quantity mismatch alarm will be
generated if the setting is incorrect.
Power module capacity (kVA)
Rated power module capacity.
Requisite modules
Match the system capacity.
Redundant modules
Set in accordance with loading capacity and redundant requirements.
Working mode
The value can be Normal mode (default), Converter mode, Self-load mode, or ECO.
BSC mode
The value can be Non-BSC (default) or BSC mode. The latter is set when the
system is a dual-bus system.
A dual-bus system consists of one master and one slave BSC system, which are
specified by the customer. A BSC system cannot be the master and slave at the same
time. Specify master and slave systems during deployment. To change the setting,