Huawei UPS5000-E Series User Manual page 247

Integrated ups, 50/125 kva
Hide thumbs Also See for UPS5000-E Series:
Table of Contents

Advertisement

UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Alarm ID
Alarm Name
(Alarm
ID-Cause
ID)
0565-1
Load impact
transfer-to-bypass
0566-1
Output overload
0570-4
BPM module
abnormal
0583-1
Inter-rack par. cable
abnormal
0583-4
Issue 09 (2019-12-20)
Severity
Cause
Derating reduces
the rated system
power.
The module is
damaged.
Minor
A large-power
RCD load is
instantly
connected, or the
output load
short-circuits.
The inverter
bridge
short-circuits.
Minor
The load is
excessive.
Derating reduces
the rated system
power.
The module is
damaged.
Critical
The bypass fan is
not functioning
properly, or the
air channel is
blocked.
The ambient
temperature
exceeds the
upper threshold.
The load is
excessive.
Critical
The inter-rack
parallel system
CAN bus is
disconnected or
short-circuited.
Only one rack
works in a
parallel system.
An ECM is
faulty.
The inter-rack
industrial frequency
Copyright © Huawei Technologies Co., Ltd.
C Alarm List
Solution
is not derated due to a fan
fault.
3. If the alarm persists, replace
the power module.
1. Check the load.
2. If the load is normal, replace
the power module.
1. Check that there is no
overload.
2. Check that the module power
is not derated due to a fan
fault.
3. If the alarm persists, replace
the power module.
1. Check the bypass fan and air
channel. If the fan is faulty,
replace it.
2. Check that the ambient
temperature has not exceeded
40° C.
3. Check that there is no
overload.
1. Check the inter-rack parallel
system CAN bus.
2. Rectify the disconnection or
short-circuit fault.
3. Replace the ECM.
Replace the inter-rack parallel
238