UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Procedure
Step 1 Switch on all SPD circuit breakers in the integrated UPS.
Step 2 Switch on the upstream power input circuit breaker for the integrated UPS to power on the
UPS cabinet. If the Power indicator in the upper part of the integrated UPS lights up, the UPS
cabinet is powered on properly.
Step 3 Turn on the circuit breakers of the ATS operation mechanism (Q1 and Q2 in the left lower
part at the rear of the cabinet) to power on the ATS operation mechanism.
Step 4 Check whether the controller has alarms. If an alarm exists, rectify the fault first.
Step 5 Press the locking latch on the ATS panel, pull out the handle, and insert it into the slot.
Step 6 Check the ATS Motor/Manual selection lever, and flip it to the Motor mode.
Step 7 Check the AC input and configuration status of the ATS.
After the AC input is normal, the ATS controller starts. Check and set ATS parameters based
on the AC input parameters.
Table 5-2 System configuration attributes and values
Item
Rated operating
voltage
Rated frequency
Number of Phases
LN1
Number of Phases
LN2
Secondary load
Issue 09 (2019-12-20)
A password is required to log in to the configurations page. Set the password by using the Up, Down,
and Enter buttons. The initial password is 0001.
Language setting: Default screen > Main Menu > Device Configuration > Language.
On the default screen, hold down
main menu screen, select system configuration and press
The following table lists the system configuration attributes and values.
Copyright © Huawei Technologies Co., Ltd.
. The main menu screen is displayed. On the
Value
110 V/57 V; 115 V/66 V; 120
V/70 V; 208 V/120 V; 220 V/127
V; 230 V/132 V; 240 V/138 V;
227 V/160 V; 347 V/200 V; 380
V/220 V; 400 V/230 V; 415
V/240 V; 440 V/254 V; 480
V/277 V
50 Hz; 60 Hz
Single phase; three-phase
four-wire; three-phase three-wire
Single phase; three-phase
four-wire; three-phase three-wire
Not Used; Opening Only;
Opening And Closing
5 Operations
.
Description
The default value is 380
V/220 V. Set the parameter
based on site requirements.
The default value is 50 Hz.
Set the parameter based on
site requirements.
The default value is
three-phase four-wire.
The default value is
three-phase four-wire.
The default value is Not
Used.
159