Huawei UPS5000-E Series User Manual page 48

Integrated ups, 50/125 kva
Hide thumbs Also See for UPS5000-E Series:
Table of Contents

Advertisement

UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Figure 2-25 ATS controller
(1) Alarm ID description
Table 2-11
Table 2-11 Alarm ID description
Alarm ID
1
2
3
4
5
6
7
Table 2-12
Issue 09 (2019-12-20)
describes the alarm IDs of the ATS controller in detail.
Power
Description
Supply
Status
No voltage
The supply voltage is less than 10% of the rated voltage.
Undervoltage
The supply voltage is less than the undervoltage threshold.
Overvoltage
The supply voltage is greater than the overvoltage threshold.
Phase
A phase of the power supply is open.
missing
Voltage
The difference between the minimum and maximum phase
unbalance
voltages of the power supply exceeds the percentage of the
overvoltage or undervoltage threshold.
Incorrect
The phase sequence of the power supply is incorrect.
phase
sequence
Invalid
The supply frequency exceeds the threshold.
frequency
describes the buttons on the ATS controller.