5.9.4.2 Download over the WebUI

Procedure
Step 1 Log in to the WebUI.
Step 2 Choose Query > Logs, select logs from the Log drop-down list box, then click Export to
export logs.
Figure 5-30 Logs
----End

5.10 Transferring to Maintenance Bypass Mode

Context
Procedure
Step 1 Manually transfer the UPS to bypass mode.
Step 2 Remove the screws using a Phillips screwdriver, remove the barrier chip on the maintenance
bypass switch, and turn on the maintenance bypass switch.
The Maint. breaker closed alarm is displayed in the alarm list.
Issue 09 (2019-12-20)
Strictly observe the following procedure to transfer the UPS to maintenance bypass mode.
Otherwise, loads may power off.
In maintenance bypass mode, the mains supplies power to the loads directly over the
maintenance bypass. If the mains is abnormal, the loads may power off.