UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Issue 09 (2019-12-20)
you must follow the guidance of maintenance engineers. Set the master and slave
BSC systems to master and slave BSC modes respectively.
Ensure that the BSC signal cable between the master and slave BSC systems is
properly connected and that BSC-related hardware is properly installed.
Paral. sys. hibernate
When the customer load is light, set parallel hibernation to alternate modules in
hibernation, which can prolong their service life and improve the system efficiency.
Module cycle hiber. period (d)
1 to 100 days can be set. The parameter 30 days is set by default.
Amb. temp. alarm thresh. (° C)
An alarm is generated when the ambient temperature reaches the preset value.
Top outlet fan
If a top outlet fan is configured, check the fan running status after enabling this
parameter.
EOD restart
The UPS transfers to battery mode when the mains becomes abnormal. When batteries
reach the EOD threshold and the bypass is disabled and EOD restart is enabled, the
UPS will restart as soon as the mains resumes.
If EOD restart is disabled, clear the alarm manually or enable the function to restart the
UPS.
EOD restart delay (min)
If EOD restart is set to Enable, the UPS starts working after EOD restart delay when
the mains recovers from an EOD power failure. The value range is 1-1440 min, and the
default value is 10 min.
Inverter async. alarm
Specifies whether the Inverter async. alarm is displayed when the inverter does not
track the bypass input. The normal power supply is not affected no matter whether you
set the parameter to Enable or Disable.
Bus overvoltage recovery
Specifies whether to automatically clear the alarm and restart the power module when
the rectifier or inverter shuts down due to a bus overvoltage alarm. If Bus overvoltage
recovery is set to Enable, the bus overvoltage alarm is automatically cleared, and the
rectifier and inverter automatically start when the bus voltage recovers (less than 420 V)
within Bus overvolt. recovery time. When Bus overvoltage recovery is set to Disable,
the bus overvoltage alarm cannot be automatically cleared, and the rectifier and inverter
cannot automatically start. The default value is Enable.
Bus overvolt. recovery time
If Bus overvoltage recovery is set to Enable, the bus overvoltage alarm is automatically
cleared, and the rectifier and inverter automatically start when the bus voltage recovers
(less than 420 V) within Bus overvolt. recovery time. The default value is 5s.
Capacitor failure detection
The default value is Enable. When Capacitor failure detection is set to Enable, the
power module performs inverter capacitor fault detection based on the settings of
Capacitor failure detection upper limit and Capacitor failure detection lower limit.
If the power module determines that the inverter capacitor is faulty, it shuts down the
inverter to prevent the fault from expanding.
Capacitor failure detection upper limit (A)
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
121