UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Figure 4-61 PDU Parameters screen 3
Figure 4-62 PDU Parameters screen 4
Issue 09 (2019-12-20)
Br. cur. shock protect (%)
Branch current shock protection alarm threshold. The value range is 150%-500%, and
the default value is 300%. When the ratio of the branch current to the rated branch
current exceeds the value of Br. cur. shock protect (%), an alarm will be generated.
X harmonics, Y harmonics, and Z harmonics
The number of three categories of harmonics is displayed. The value range is 2-63. The
default values of X harmonics, Y harmonics, and Z harmonics are 5, 7, and 11,
respectively. The system displays the harmonics settings in Cabinet Input.
Harmonic alarm enable
Specifies whether harmonic alarming is enabled. It is disabled by default. When
harmonic alarming is enabled, an alarm (voltage or current harmonic alarm) will be
generated if the alarm conditions are met. When harmonic alarming is disabled, no
harmonic alarm will be generated under any condition.
System overfrequency threshold (Hz)
System over/underfrequency alarm threshold. The value range is 1.0-10 Hz, and the
default value is 1.5 Hz. When the system frequency is higher than the rated frequency
plus the value of this parameter or is lower than the rated frequency minus the value of
this parameter, an alarm is generated.
Branch breaker open alarm enable
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
137