Huawei UPS5000-E FM Series User Manual

Hide thumbs Also See for UPS5000-E FM Series:
Table of Contents

Advertisement

Quick Links

UPS5000-E-(30 kVA-120 kVA)-FM
User Manual
Issue
02
Date
2020-11-10
HUAWEI TECHNOLOGIES CO., LTD.

Advertisement

Table of Contents
loading

Summary of Contents for Huawei UPS5000-E FM Series

  • Page 1 UPS5000-E-(30 kVA-120 kVA)-FM User Manual Issue Date 2020-11-10 HUAWEI TECHNOLOGIES CO., LTD.
  • Page 2 Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
  • Page 3: About This Document

    Indicates a hazard with a low level of risk which, if not avoided, could result in minor or moderate injury. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 4 Issue 02 (2020-11-10) Adapted the UPS to SmartLi and updated the monitoring user interfaces. Issue 01 (2020-04-27) This issue is the first official release. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 5: Table Of Contents

    2.3.4 Power Distribution Module............................28 2.3.5 Control Module.................................. 28 2.3.5.1 Overview................................... 28 2.3.5.2 ECM..................................... 29 2.3.5.3 Dry contact card................................31 2.3.5.4 Monitoring interface card............................33 2.3.6 MDU....................................... 38 2.4 Typical configurations................................. 40 Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 6 4.1 LCD Interface..................................87 4.1.1 Main Menu..................................87 4.1.2 System Info Screen................................88 4.1.2.1 Module Data Screen..............................89 4.1.2.2 Running..................................... 89 4.1.2.3 Alarms Screen..................................93 4.1.2.4 Settings....................................94 4.1.2.5 Maintenance..................................118 4.1.2.6 About Screen................................. 123 Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 7 5.11 Exporting Data.................................. 160 5.12 Setting Hibernation Mode............................161 6 Routine Maintenance......................163 6.1 UPS Maintenance................................163 6.1.1 Monthly Maintenance..............................164 6.1.2 Quarterly Maintenance..............................164 6.1.3 Annual Maintenance..............................165 6.2 Battery Maintenance................................. 166 Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 8 8.6 Bypass Input Electrical Specifications.......................... 175 8.7 Battery Electrical Specifications............................. 176 8.8 Output Electrical Specifications............................. 177 8.9 System Electrical Specifications............................. 178 A (Optional) TN-C System Application................179 B Alarm List..........................180 C Acronyms and Abbreviations................... 193 Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 9: Safety Information

    The "NOTICE", "CAUTION", "WARNING", and "DANGER" statements in this document do not cover all the safety instructions. They are only supplements to the safety instructions. Huawei will not be liable for any consequence caused by the violation of general safety requirements or design, production, and usage safety standards.
  • Page 10 ● Keep irrelevant people away from the equipment. Only operators are allowed to access the equipment. ● Use insulated tools or tools with insulated handles, as shown in the following figure. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 11 Do not change the structure or installation sequence of equipment without permission. ● Do not touch a running fan with your fingers, components, screws, tools, or boards before the fan is powered off or stops running. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 12: Personnel Requirements

    Do not power on the equipment before it is installed or confirmed by professionals. 1.2 Personnel Requirements ● Personnel who plan to install or maintain Huawei equipment must receive thorough training, understand all necessary safety precautions, and be able to correctly perform all operations. ●...
  • Page 13 0°C. Handle cables with caution, especially at a low temperature. – Cables stored at subzero temperatures must be stored at room temperature for at least 24 hours before they are laid out. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 14: Installation Environment Requirements

    Install the equipment in an area far away from liquids. Do not install it under areas prone to condensation, such as under water pipes and air exhaust vents, or areas prone to water leakage, such as air conditioner vents, ventilation Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 15 Any violations must be promptly pointed out by the site manager or safety supervisor and the involved personnel should be prompted for correction. Personnel who fail to stop violations will be forbidden from working. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 16: Mechanical Safety

    Ensure that the wider end of the ladder is at the bottom, or protective measures have been taken at the bottom to prevent the ladder from sliding. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 17 D ANGER When removing a heavy or unstable component from a cabinet, be aware of unstable or heavy objects on the cabinet. ● Be cautious to avoid injury when moving heavy objects. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 18: Device Running Safety

    The UPS operating environment must meet the requirements for the climate indicator, mechanically active substance indicator, and chemically active substance indicator in ETSI EN 300 019-1 class 3.6. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 19 UPS is connected to a backfeed protection card. Disconnect the backfeed protection card from the UPS before operating the UPS. Do not use the UPS in the following places: Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 20: Battery Safety

    ● Dispose of waste batteries in accordance with local laws and regulations. Do not dispose of batteries as household waste. If a battery is disposed of improperly, it may explode. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 21 NO TICE To ensure battery safety and battery management accuracy, use batteries provided with the UPS by Huawei. Huawei is not responsible for any battery faults caused by batteries not provided by Huawei. Battery Installation Before installing batteries, observe the following safety precautions: ●...
  • Page 22 Use batteries within the allowed temperature range; otherwise, the battery performance and safety will be compromised. ● Do not throw a lithium battery in fire. ● When maintenance is complete, return the waste lithium battery to the maintenance office. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 23: Others

    UPS output voltage level or frequency. Doing so may affect the power supply to equipment. ● Exercise caution when setting battery parameters. Incorrect settings will affect the power supply and battery lifespan. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 24: Overview

    Product 5000 family E series subcategory Output 120K: output capacity of 120 kVA (compatible with 90 capacity kVA, 60 kVA, and 30 kVA) Configuration F: in full configuration type M: modular Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 25: Working Principle

    In normal mode, the rectifier converts AC power into DC power, then the inverter converts DC power into high-precision AC outputs. The conversions protect loads from interference such as input harmonics, glitches, and voltage transients. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 26: Bypass Mode

    The bypass power supply is not protected by the UPS which means it may be affected by mains outage, and incorrect AC voltage or frequency. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 27: Battery Mode

    If the mains input is abnormal or the rectifier becomes abnormal, the UPS transfers to battery mode. The power module obtains DC power from batteries, and the power is converted into AC output by the inverter. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 28: Maintenance Bypass Mode

    2.2.2.4 Maintenance Bypass Mode When the UPS works in maintenance bypass mode, the current flows through the maintenance bypass instead of the power module. You can maintain the circuit inside the cabinet. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 29: Eco Mode

    UPS transfers from bypass mode to normal mode. In bypass mode or normal mode, the rectifier keeps working and charges batteries using a charger. The ECO mode delivers a high efficiency. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 30: Product Introduction

    Figure 2-7 UPS conceptual diagram in ECO mode NO TE Manual startup is required to ensure that the inverter is in standby state and the power flow has reached the inverter. 2.3 Product Introduction Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 31: Structure

    (4) Bypass input switch bypass switch (5) Mains input switch (6) Surge protective (7) Control module (8) Bypass module module (optional) (9) Power modules (10) Monitor display (11) Folder module (MDU) Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 32: Power Module

    (blinking at 0.5 Hz, on for 1s intervals and off for 1s). ● The inverter is not started (blinking at 0.2 Hz, on for 2.5s and off for 2.5s). Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 33 Dimensions (H x W x D): 86 mm x 442 mm x 620 mm ● Weight: < 21 kg ● Rated output capacity: 30 kVA/30 kW ● Power density: 20.64 W/inch Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 34: Bypass Module

    Run indicator Green Steady on The system is working in bypass mode. Blinking at long The bypass has no output intervals (blinking at 0.2 Hz, on for 2.5s and off for 2.5s). Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 35 A manual operation is performed to transfer to bypass mode. Specifications ● Dimensions (H x W x D): 130 mm x 420 mm x 500 mm ● Weight: 19 kg ● Rated output capacity: 200 kVA Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 36: Power Distribution Module

    (from left to right). The four cards are hot swappable. One subrack is reserved above the dry contact card. A backfeed protection card or dry contact extended card can be inserted into this subrack. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 37: Ecm

    The control module consists of two energy control modules (ECMs) in active/ standby mode. Figure 2-13 ECM Table 2-4 Ports on the ECM Silk Screen Description PARALLEL The PARALLEL port transmits parallel signals between racks. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 38 Controls the running of a single UPS5000 and a parallel system, and reports the UPS5000 status information to other monitoring modules. ● The system provides three types of CAN communication: monitoring CAN communication, intra-rack parallel CAN communication, and inter-rack parallel CAN communication. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 39: Dry Contact Card

    Port for signal ground ● Disconnected: no battery grounding fault Port for detecting diesel ● Connected: D.G. Disconnecte generator (D.G.) mode mode ● Disconnected: Port for signal ground non-D.G. mode Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 40 STATUS_MT maintenance circuit circuit breaker breaker ● Connected: SWITCH Port for signal ground circuit breaker STATUS_0V SWITCH Port for monitoring the ● Connected: Connected STATUS_BP bypass input circuit circuit breaker breaker Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 41: Monitoring Interface Card

    ● In a parallel system, ensure that used dry contacts properly connect to each UPS. The monitoring interface card provides external ports as well as monitoring and control functions for the MDU. The ports include the ambient temperature and Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 42 B_TEMP Connects to an indoor battery temperature sensor port sensor. Southbound COM1 ● Supported protocol: Modbus-RTU. communications ● Connects to an ambient temperature and port 1 humidity sensor over two wires. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 43 ● RS485 cables and FE cables must be shielded cables. Figure 2-17 Figure 2-18 are recommended wiring methods for DO ports. Figure 2-17 Wiring method 1 Figure 2-18 Wiring method 2 Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 44 UPS5000-E-(30 kVA-120 kVA)-FM User Manual 2 Overview Figure 2-19 COM1 pins Table 2-8 COM1 pin definition Description RS485– RS485+ 12V_PORT Figure 2-20 COM2 pins Table 2-9 COM2 pin definition Description RS485+ RS485– Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 45 UPS5000-E-(30 kVA-120 kVA)-FM User Manual 2 Overview Description RS485+ RS485– CANH0 CANL0 Figure 2-21 RS485 pins Table 2-10 RS485 pin definition Description RS485_T+ RS485_T– RS485_R+ RS485_R– Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 46: Mdu

    The UPS is running properly or a warning has been generated. The MDU is powered off. NO TE The indicator on the MDU panel is yellow when the bypass supplies power in non-ECO mode. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 47 View or obtain UPS running information during preventive maintenance. NOTE Only Huawei service engineers or authorized service engineers are allowed to use the WiFi module. To ensure security, remove the WiFi module immediately after use.
  • Page 48: Typical Configurations

    UPS are connected over parallel cables. The parallel connections synchronize the UPS outputs to supply power to loads. If one UPS fails, the other UPSs continue supplying power to loads. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 49: Dual-Bus System

    An optional static transfer switch (STS) can be installed to start the bus synchronization controller (BSC). The UPS systems work in normal mode or bypass mode. Figure 2-25 Conceptual diagram of a dual-bus system Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 50: Optional Components

    Backfeed UPSDSDRYIO00 Detects mains and bypass backfeed and protection provides protection. card Antiseismic Reinforces the cabinet so that the cabinet meets the requirements of 9 degree seismic fortification intensity. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 51 NO TE The ECM extended subrack does not support onsite installation. If you require this optional component, inform Huawei when you purchase the UPS. Huawei installs it before delivery. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 52: Installation

    Ensure that the floor or installation support can bear the weight of the UPS5000, batteries, and battery racks. The weight of batteries and battery racks depends on the UPS configuration for the site. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 53: Installation Environment

    The optimal operating temperatures for valve-regulated lead-acid batteries (VRLA batteries) are 20–30°C. Operating temperatures higher than 30°C shorten the battery lifespan and operating temperatures lower than 20°C reduce the battery backup time. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 54: Installation Clearances

    Insulate installation tools to prevent electric shocks. Prepare the following tools and meters indicated in Table 3-1 for installation. Table 3-1 Tools and meters Tools and Meters Electric pallet Manual pallet Ladder Rubber mallet truck truck Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 55 Level instrument Polyvinyl chloride Cotton cloth Label Electrician's knife (PVC) insulation tape Electrostatic Protective gloves Insulated gloves Insulation discharge (ESD) protective shoes gloves Torque Cable cutter Brush Flat-head screwdriver screwdriver (2–5 mm) Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 56: Preparing Power Cables

    Specifications 30 kVA 60 kVA 90 kVA 120 kVA Mains Mains input current (A) input Recommended 4 x 10 4 x 35 4 x 70 4 x 95 cross-sectional area (mm Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 57 IEC-60364-5-52 or the local regulations. ● If the rated voltage is 400 V, multiply the currents by 0.95. If the rated voltage is 415 V, multiply the currents by 0.92. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 58 Table 3-4 Recommended upstream input and downstream output circuit breakers UPS Capacity Component Specifications 30 kVA Mains input circuit breaker 63 A/3P Bypass input circuit breaker 63 A/3P Downstream output circuit 63 A/3P breaker Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 59: Unpacking And Checking

    Keep the UPS steady during unpacking. ● To prevent dust from settling on the UPS, leave the original plastic coat on until installation is required. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 60 Step 4 Remove packing materials, as shown in Figure 3-4. Figure 3-4 Removing packing materials Step 5 Remove the plastic bag and take out the fittings box. Step 6 Check that the UPS is intact. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 61 Check that all fittings comply with the packing list. If some fittings are missing or do not comply with the packing list, record this information and contact your local Huawei office immediately. Step 7 After confirming that the UPS is intact, remove the front and rear L-shaped brackets that secure the UPS to the pallet, and secure the sliding plate to the pallet using the two M12 bolts removed before.
  • Page 62 Ensure that the two screws are installed reliably. Otherwise, the sliding plate may shift when the UPS slides down. Step 8 Raise the four anchor bolts to the highest position using an adjustable wrench, as shown in Figure 3-7. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 63: Installing A Single Ups

    3.2 Installing a Single UPS 3.2.1 Installing the Cabinet Secured Installation Step 1 Determine the position for installing the cabinet. Mark mounting holes for the UPS based on the following figures: Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 64 (4) Expansion sleeve NO TICE Ensure the expansion tube of the expansion bolts fits completely into the hole. The expansion sleeves must be completely buried under the ground to properly facilitate subsequent installation. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 65 Step 4 (Optional) If the castors of the UPS need to be lifted from the ground, perform steps Step 1 Step 2 Unsecured Installation. Step 5 Remove the rear panel of the cabinet, and then open the front door. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 66 Step 6 Remove the four plugs from the bottom of the cabinet (two at the front and two at the rear). Figure 3-12 Removing plugs Step 7 Insert four M12x115 expansion bolts into the expansion bolt holes in the floor, and tighten the expansion bolts in the direction. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 67 Figure 3-14. Figure 3-14 Castors adjustment Step 2 Check the cabinet levelness using a level. If the cabinet is not level, wrench the anchor bolts. ----End Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 68: Installing Batteries

    Figure 3-15 Antiseismic kit mounting hole positions Step 2 Secure two antiseismic kits to the front and rear of the cabinet using twelve M5x16 screws and four M12 screws. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 69: Connecting An Ambient T/H Sensor

    Figure 3-17 Securing the antiseismic kits to the floor ----End 3.2.3.2 Connecting an Ambient T/H Sensor Procedure Step 1 Connect the RJ11 port on the ambient T/H sensor to the COM1 port on the monitoring interface card. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 70: Connecting The Ibat

    Figure 3-19 COM2 port ----End 3.2.3.4 Installing a Battery Grounding Failure Detector Procedure Step 1 Install a battery grounding failure detector. For the installation method, see Battery Grounding Failure Detector User Manual . Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 71: Ups Cable Connection Reference

    Step 3 Pull the marked cable out of the cabinet, cut the cable from the marked position, strip the cable, and crimp a terminal. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 72: Routing Cables

    Step 1 Ensure the maintenance bypass switch is OFF. Open the front door, remove the front cover, and remove covers from the top of the cabinet based on the site requirements. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 73 (1) Battery input terminals (+, N, –) (2) Mains input terminals (1L1–1L3, N) (3) Bypass input terminals (2L1–2L3, N) (4) Output terminals (U, V, W, N) Step 2 Connect ground cable. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 74 UPS5000-E-(30 kVA-120 kVA)-FM User Manual 3 Installation Figure 3-24 Grounding Step 3 Route power cables. ● Dual mains Remove the copper bar between mains and bypass input terminals. Figure 3-25 Removing copper bars Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 75 For single mains, the copper bar between the mains and bypass input terminals do not need to be removed, and bypass input cables do not need to be connected. Step 4 Route signal cables. Bind cables to the cabinet. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 76: Routing Cables From The Bottom

    Route cables for the UPS from inside out. Procedure Step 1 (Optional) Determine the installation position for the cable entry cabinet, and draw mounting holes in the installation position based on drawings. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 77 Step 3 Adjust the anchor bolts of the cable entry cabinet to make it flush with the UPS cabinet. Step 4 Install equipotential plate mounting kits on the same horizontal plane of the UPS cabinet and cable entry cabinet. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 78 Figure 3-30 Installing equipotential plate mounting kits (1) Side panel (2) Cable trough Step 5 Place the cable entry cabinet on the right of the UPS cabinet. Step 6 Install the front and rear connecting kits. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 79 Step 7 (Optional) Secure the cable entry cabinet to the ground. NO TE For details about how to secure the cable entry cabinet, see Secured Installation 3.2.1 Installing the Cabinet. Step 8 Install an equipotential plate. Figure 3-32 Equipotential plate Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 80 Remove the two large covers from the bottom of the cable entry cabinet, drill holes in them based on site requirements, and install them on the positions where the small covers were placed. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 81 For the screw specifications and torque used for connecting cables in a bottom cable routing scenario, refer to the top cable routing scenario. This section only shows the cable routes in the bottom cable routing scenario. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 82 UPS5000-E-(30 kVA-120 kVA)-FM User Manual 3 Installation Figure 3-36 Connecting cables Step 12 Remove the signal cable trough cover from the cable entry cabinet. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 83 Step 13 Connect the signal cable. (Route the signal cable out of the UPS cabinet through the cable hole on the top, and then into the cable entry cabinet through the cable hole on the top of that cabinet.) Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 84: Remote Epo

    ----End 3.2.6 Remote EPO NO TICE ● Huawei does not provide the EPO switch or cable. If the cable is required, the recommended cable is 22 AWG. ● Equip the EPO switch with a protective cover to prevent misoperations, and cover the cable with protective tubing.
  • Page 85: Connecting Communications Cables

    Step 1 Connect the external network management device to the RS485 port of the monitoring interface card. Step 2 Connect the network port on a PC to the FE port of the monitoring interface card. ----End 3.3 Installing a Parallel System Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 86: Installing The Upss

    UPSs and then tighten the screws on the kit, as shown in Figure 3-41. Figure 3-41 Connecting parallel plates NO TE You also need to connect parallel plates at the rear of the UPS. ----End Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 87: Connecting Power Cables

    Figure 3-42 shows a typical conceptual diagram for a 1+1 parallel system, and Figure 3-43 shows the cable connections for this system. Figure 3-42 Conceptual diagram of a 1+1 parallel system Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 88 UPS systems, and Figure 3-45 shows the cable connections for this system. Figure 3-44 Conceptual diagram of a dual-bus system Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 89: Connecting Signal Cables

    Step 1 Connect the parallel ports on the UPSs using parallel cables to form a loop. ● Figure 3-46 shows the topology diagram for the N+X parallel system and Figure 3-47 shows the cable connections for this system. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 90 +X parallel system ● In a dual-bus system, you need to connect cables to BSC ports on the UPSs. Figure 3-48 shows the cable connections for a dual-bus system containing two master systems. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 91: Installation Verification

    UPS may be damaged. Table 3-5 Installation checklist Item Acceptance Criteria UPS installation The UPS is securely installed and does not tilt due to vibration. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 92 4. Ensure that there is no foreign matter on the bottom plate of the cabinet. 5. Ensure that there is no foreign matter on the rear module subrack. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 93 Figure 3-49 Positions to be checked for foreign matter (1) Rear of modules (2) Cabinet top (3) Wiring terminal (4) Switches blocks Figure 3-50 Fill the holes with sealing putty (1) Paper protective film (2) Sealing putty Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 94 UPS5000-E-(30 kVA-120 kVA)-FM User Manual 3 Installation Figure 3-51 Dustproof cover (1) Dustproof cover Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 95: User Interface

    The LCD screen is divided into three parts: status bar, alarm bar and information area. Figure 4-1 numerically labels functions of the default main screen, and Table 4-1 describes these functions. Figure 4-1 Main Menu screen Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 96: System Info Screen

    Scrolls the page down. Scrolls the page up. Returns to the upper-level menu. Logs a user out. 4.1.2 System Info Screen On the main screen, tap System Info. The System Info screen is displayed. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 97: Module Data Screen

    Figure 4-3. Figure 4-3 Module Data screen 4.1.2.2 Running On the System Info screen, tap to access the Runn Info screen. Figure 4-4 Running 1 Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 98 Active power (kW) Output active power of each phase on the UPS. Apparent power (kVA) Output apparent power of each phase on the UPS. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 99 Bypass input line voltage Phase current (A) Bypass input phase current Frequency (Hz) Bypass input frequency Power factor Proportion of the bypass input active power to the bypass input apparent power. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 100 ● If the value is less than 1, the value takes 0. ● If the value is greater than or equal to 1 and less than 2, the value takes 1. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 101: Alarms Screen

    System Info screen to enter the Alarms screen. Figure 4-6 Alarms Screen Active alarms This screen displays alarm information including the severity, name, ID, location, and generation time. Figure 4-7 Active alarms Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 102: Settings

    When the UPS communicates with the northbound NMS, the function determines the position of the UPS in the NMS layout diagram. 4.1.2.4 Settings On the System Info screen, tap to access the Settings screen. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 103 UPS5000-E-(30 kVA-120 kVA)-FM User Manual 4 User Interface Figure 4-9 Settings 1 Figure 4-10 Settings 2 Comm Settings Figure 4-11 Comm. Settings (lead-acid battery) Figure 4-12 Comm. Settings (lithium battery) Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 104 10110110.01100010.1 operation result 1100001.01000000 1100001.01000000 – Automatic: The MDU automatically searches for available IP addresses in the connected network. Ensure that the MDU and PC are on the same network segment. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 105 Value Range Address This serial port address is 1–254 allocated by the user. Baud rate Select a baud rate to match 9600 9600, 19200, the user's network 115200 management conditions onsite. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 106 Default Value Value Range ModbusTCP If Modbus TCP is used for Enable Disable, encryption communication, Enable communication links do not implement encryption or implement encryption based on the selected encryption mode. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 107 Number of cascaded ambient 0–4 temperature and humidity sensors Figure 4-17 Battery temperature sensor Item Description Default Value Value Range Start address 16–28 Quantity Number of cascaded battery 0–4 temperature sensors Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 108 Last six set WiFi SSID after characters of connecting a WiFi module the MAC over a USB port to identify address the WiFi device to which the mobile phone is connected. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 109 UPS through a only browser. Disable: The HTTPS services are unavailable. Read-only: Only operator users are allowed to access the services and have only the read permission. Enable: All functions are available. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 110 Read-only: Only the read permission is enabled. Settings are not allowed. NetEco: The read permission and the write permission on related parameters supported by the NetEco are enabled. Enable: All functions are available. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 111 Figure 4-21 Battery System Item Description Default Value Value Range SmartLi start SmartLi communication address address when the UPS queries SmartLi data System Settings Figure 4-22 System settings 1 Figure 4-23 System settings 2 Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 112 ±7%, ±8%, bypass voltage and the rated ±9%, ±10% voltage is greater than this value, the system determines that the ECO voltage is abnormal and transfers to normal mode. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 113 (or delay (s) module) transfers from battery mode to normal mode, which reduces the impact on the generator or power grid. In the case of battery undervoltage, the system automatically Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 114 D.G. mode Set this parameter to Enable Disable Disable, when a D.G. connects to the Enable input PDC. The UPS enters the D.G. mode when a D.G. is detected over dry contacts. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 115 (If the voltage level is 380 V or 400 V, the default upper limit is +15%. If the voltage level is 415 V, the default upper limit is +10%.) Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 116 EOD restart is Enable, the UPS will restart as soon as the mains resumes. If EOD restart is disabled, clear the alarm manually or enable the restart function for the UPS. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 117 +10%, +15%, and +20%. The unavailable. default value is +15%. ● When the voltage level is 415 V, the value range is +10% and +15%. The default value is +10%. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 118 Each cell has a nominal voltage of 2 V. A battery is a module consisting of single or multiple cells in a shell. Each battery has a nominal voltage of 2 V, 6 V, or 12 V. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 119 Number of Specifies the number of Depends on 1–6 battery battery strings connected in the actual strings parallel. model. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 120 Shallow dis. Specifies the proportion of 10–50 test dis. the discharge capacity to the ratio(%) total discharge capacity. The value is configurable in any mode. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 121 On the System Info > Settings > iBOX Settings > Basic Param. screen, if the Number of iBOXs is not 0 the Batt. String Config is displayed on the iBOX Settings screen. Figure 4-31 Basic Param. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 122 Hall effect sensors hall at the positive or negative terminal of a battery string (Single batt. group number of hall≥ 1). Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 123 MUE05A connection Specifies the MUE05A connection status. Independent input signals can be enabled only when this parameter is set to Enable. Batter ground fault [BTG] Enable or disable battery grounding fault detection. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 124 MUE07A DO_3 Action, MUE07A DO_4 Action, MUE07A DO_5 Action MUS05A DO_1, MUS05A Corresponds to the signal of the output dry DO_2, MUS05A DO_3, contact DO on the MUS05A. MUS05A DO_4 Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 125 Figure 4-34 User settings Item Description Default Value Value Range Language Thirteen languages are English English, supported Chinese, Spanish, Dutch, French, German, Italian, Polish, Portuguese, Russian, Swedish, Turkish, Japanese Password 000001 Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 126: Maintenance

    Set the local time zone. ● You can enable DST in areas where DST is used. 4.1.2.5 Maintenance On the System Info screen, tap to display the Maintenance screen. Figure 4-36 Maintenance 1 Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 127 This reduces the discharge time before the next charge. ● Do not perform battery maintenance when a D.G. is connected. Battery maintenance includes Forced Equalized Charging, Shallow Dis. Test, and Capacity Test. Figure 4-38 Battery Maint. (lead-acid battery) Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 128 USB Operations You can export Fault Data, and perform Upgrade Software, BSP Upgrade, Export Config., and Import Config. with USB. Figure 4-40 USB Operations Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 129 Bus capacitor life forecast If the service life of a capacitor is about to end, that is, Module X bus capacitor life (y) is less than 1.0, contact Huawei technical support to replace the power module. Issue 02 (2020-11-10)
  • Page 130 Enable, and set BCB connection [OL] to Enable. Wizard-based startup can be used to test the battery switch tripping function. Lifecycle On Lifecycle, you can view monitor information such as First Power-on, Arrival Date, and Service Life. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 131: About Screen

    Version Info. Figure 4-42 About screen 4.1.3 System Status On the System Status to view the mains input, bypass input, load, and battery information. Figure 4-43 System status 4.1.4 Common Functions Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 132: Webui

    Step 1 Open the browser and choose Tools > Internet Options. Step 2 On the Advanced tab page, ensure that Use TLS 1.0, and Use TLS 1.1 are selected and click OK. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 133 (common user) exports system information, starts/shuts down the inverter, rectifies faults, and controls the buzzer. Other control and maintenance functions that may affect system operation are invisible and parameters cannot be set. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 134: Monitoring

    Set Running Parameter for the ECM. Battery System View the battery Running Information and set Running Parameter. Battery String Set parameters for the iBOX and iBAT connected to each Summary battery string. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 135 ECO function is enabled. ● If this parameter is set to Disable, the system is not allowed to enter ECO mode when the D.G. supplies power to the bypass. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 136 If this parameter is set to Disable Disable, current if no Enable, the current at no Enable load load will be calibrated once automatically. This function can be used only when the UPS carries no load. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 137 LCD when the inverter cannot track the bypass frequency change. Normal power supply is not affected no matter whether this parameter is set to Enable or Disable. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 138 Capacitor failure detection upper limit and Capacitor failure detection lower limit. If the power module determines that the inverter capacitor is faulty, it shuts down the inverter to prevent the fault from expanding. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 139 (Charge/Discharge voltage – Average voltage)/Average voltage x 100%. The charge/discharge voltage and average voltage are obtained from the BMU. If the BMU is not configured, these two parameters do not need to be set. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 140 Equalized charging protection protection interval. After interval (d) equalized charging is complete, scheduled equalized charging starts when the non-equalized charging time exceeds Scheduled equalized charging interval. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 141 When a value exceeds the specified range, an alarm is generated. The calculation formula is (Charge/Discharge voltage – Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 142 Class 1 grid Hibernation time for class 1 0–30 hiber. time power grids. Class 2 grid Hibernation time for class 2 0–15 hiber. time power grids. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 143: Query

    End number of an iBAT connected to the iBOX. 4.2.3 Query On the Query page, you can query Historical Alarm, Battery Test Records, and Performance Data, and perform Export Data. Figure 4-48 Query Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 144: System Settings

    Export Historical Alarm, Active Alarm, Operation Log, and Performance Data. 4.2.4 System Settings Figure 4-49 System settings (lead-acid battery) Figure 4-50 System settings (lithium battery) Site Configuration Table 4-16 System type Item Description Name Site name. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 145 Users can replace the UPS certificate with a trusted certificate. Upload key file Key file of the certificate. Key password Decryption password of the key. Confirm key password Confirm the decryption password of the key. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 146 Alarm Notification User Settings. ● After the Event Notice information is configured, alarms will be sent to the configured mailbox. Outbox configuration Table 4-19 Outbox settings Item Description Address type IP address is supported. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 147: Maintenance

    Query and export E-labels of devices in the system. User Users can add, modify, delete, lock, and unlock operations, Management and set passwords. Fault Information Export fault information. BSP Upgrade Upgrade the BSP version. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 148 UPS5000-E-(30 kVA-120 kVA)-FM User Manual 4 User Interface Item Description Lifecycle View monitor information such as First Power-on, Arrival Date, and Service Life. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 149: Operations

    Step 2 (Optional) If a surge protective module is configured, turn on its switch. Step 3 Close the UPS bypass input switch, mains input switch, and output switch. After the UPS is powered on, initialization begins. The MDU displays the Huawei logo and an initialization progress bar.
  • Page 150: Obtaining Startup Password

    Enter the generated password in the password text box on the LCD to start the inverter. ----End 5.1.2.2 Settings Wizard Procedure Step 1 Set the language, time, network parameters, system parameters, and battery parameters on the Settings Wizard screen. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 151 ● Set Output frequency correctly; otherwise, loads may be affected and the UPS may not work properly. ● Battery parameter settings are critical to battery maintenance, battery lifespan, and UPS discharge time. Figure 5-1 Settings Wizard Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 152: Starting The Inverter

    NO TE You can also start the inverter by choosing System Info > Maintenance > Inv. ON. Step 2 In the displayed login screen, select a user name and enter the password. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 153 Step 5 On the home page of the WebUI, choose Monitoring > UPS System > Running Control, click Inv. ON, and confirm the operation to start the inverter. Figure 5-3 Starting the inverter Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 154: Powering On Loads

    Step 1 On the System Info > Settings > Dry Contact Set screen, set MUE05A connection to Enable, and set BCB connection [OL] and Battery breaker [STA] to Enable. Figure 5-4 BCB connection setting ----End Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 155: Shutting Down And Powering Off The Ups

    To shut down the inverter on the Maintenance screen, tap System Info > Maintenance. Figure 5-5 Normal bypass NO TE After you shut down the inverter, the Bypass mode alarm is displayed on the LCD. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 156: Cold-Starting The Ups Using Batteries

    (single battery voltage x number of batteries in the battery string). Open the upstream mains input and bypass input switches, and close the battery circuit breaker. If there are multiple battery strings, close the circuit Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 157: Transferring To Bypass Mode

    Press and hold down the BATT START button on the bypass module for at least 2 seconds. The system automatically enters the battery cold start status. The LCD displays the Huawei logo and an initialization progress bar. After LCD initialization, start the inverter on the LCD.
  • Page 158 After the inverter starts, the UPS still works in bypass mode and the inverter is on standby. If the bypass is not normal, the inverter supplies power immediately. If the inverter is not started, the UPS may be disconnected. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 159: Testing Batteries

    Step 1 On the home screen of the LCD, choose System Info > Maintenance > Battery Maint. Step 2 Tap Start next to Forced Equalized Charging to start a forced equalized charging test. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 160: Shallow Discharge Test

    After setting is complete, the system will perform automatic shallow discharge tests based on the settings. ----End Manual Shallow Discharge Test Step 1 On the home screen of the LCD, choose System Info > Maintenance > Battery Maint. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 161: Capacity Test

    ● The mains, batteries, charger, and discharger are normal. No overload alarm is generated. Procedure Step 1 On the home screen of the LCD, choose System Info > Maintenance > Battery Maint. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 162: Lithium Battery Test

    No generator is connected to the UPS. ● The mains, batteries, charger, and discharger are normal. No overload alarm is generated. ● The SmartLi has generated no alarms related to lithium batteries. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 163: Capacity Test

    ● The battery discharge capacity reaches the specified value (10%–50%, 20% by default). ● The discharge voltage reaches the warning threshold (calculated in real time). ● The load ratio fluctuation exceeds 10%. ● An alarm is generated. 5.6.2.2 Capacity Test Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 164: Test Data Download

    The test is complete when the minimum cell voltage reaches 2.6 V. Data about the most amount of energy discharged is stored once a month for 36 months. ----End 5.6.3 Test Data Download Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 165: Transferring To Maintenance Bypass Mode

    The maintenance bypass switch in the figures below is for reference only. Close the maintenance bypass switch according to site specifications. The Maint. breaker closed alarm is displayed in the alarm list, as shown in Figure 5-16. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 166 Figure 5-15 Closing the maintenance bypass switch Figure 5-16 Maint. breaker closed alarm NO TE After the UPS transfers to maintenance bypass mode, the Maint. breaker closed and Bypass mode alarms are displayed on the LCD. ----End Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 167: Transferring From Maintenance Bypass Mode To Normal Mode

    EPO button is turned on. Press the external EPO switch that connects to the dry contact card or remove the 4-pin terminal on the EPO port of the dry contact card. Figure 5-17 EPO ports Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 168: Clearing The Epo State

    The following data can be exported: ● Historical Alarm ● Active Alarms ● Performance Data ● Operation Log ● E-Label ● Fault Information NO TE This topic describes how to export historical alarms. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 169: Setting Hibernation Mode

    On the WebUI, choose Monitoring > UPS System > Running Parameter > System Settings and set Paral sys hibernate to Enable. Set the module cycle hibernation period to an integer ranging from 1 to 100. The default value is 30. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 170 UPS5000-E-(30 kVA-120 kVA)-FM User Manual 5 Operations Figure 5-19 Running Parameter NO TE Click Submit after setting parameters on the WebUI. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 171: Routine Maintenance

    Customers are not allowed to maintain components behind protective covers that can be removed only using tools. If the components are to be maintained, contact Huawei technical support. ● Only maintenance engineers can maintain power modules and bypass modules.
  • Page 172: Monthly Maintenance

    Wipe the cabinet surface using Remove the dust, especially a white paper and the paper from the air filter on the front does not turn black. door, or replace the air filter. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 173: Annual Maintenance

    The circuit breakers and ● Replace the circuit breaker through-current cables meet load breaker. capacity requirements. ● Replace the cable. The actual cable through-current capacity is greater than the circuit breaker specifications. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 174: Battery Maintenance

    6.2.2 Monthly Maintenance Table 6-4 Monthly maintenance Item Expected Result Troubleshooting Battery No battery management Identify the cause of an alarm management alarm is generated. based on the alarm alarm information. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 175 2. Check whether the equalized charging voltage and float charging voltage are correctly set for the UPS. 3. If the fault persists, contact Huawei technical support. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 176: Quarterly Maintenance

    3. If the fault persists, contact Huawei technical support. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 177: Annual Maintenance

    (A torque wrench is used for checking the torque. After checking that the battery screws meet the requirements, mark the screws for later check.) Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 178: Troubleshooting

    EOD voltage and 11.3 V/cell. For details about how to rectify common faults, see Table 7-1. If any unmentioned faults occur, see the alarm list chapter, or contact Huawei technical support. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 179 The buzzer is The bypass thyristor Replace the bypass bypass is activated, and the is damaged. module. Fault indicator is on. normal. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 180 Measure The bypass module Reduce the load, or experiences improve ventilation. overtemperature. NO TE For details about component replacement and maintenance involved in Troubleshooting and Alarm List, consult Huawei maintenance engineers. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 181: Technical Specifications

    8.2 Internal Switch Parameters Switch Specifications Maintenance 690 V AC/250 A/3P bypass switch Mains input 690 V AC/250 A/3P switch Bypass input 690 V AC/250 A/3P switch Output switch 690 V AC/250 A/3P Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 182: Environmental Specifications

    EN/IEC62040-2 Radiated emission (RE) EN/IEC62040-2 Low-frequency signal IEC61000-2-2 interference Electrostatic discharge IEC61000-4-2 immunity Conducted susceptibility EN/IEC62040-2 EN/IEC61000-4-6 Radiated susceptibility EN/IEC62040-2 EN/IEC61000-4-3 Electrical fast transient EN/IEC62040-2 (EFT) IEC61000-4-4 Surge protection EN/IEC62040-2 IEC61000-4-5 Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 183: Mains Input Electrical Specifications

    The UPS supports the SmartLi. For details about the parameters, see the SmartLi user manual. Item Specifications Rated input voltage 380 V AC, 400 V AC, or 415 V AC (line voltage) Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 184: Battery Electrical Specifications

    ● Equalized charging voltage: 2.3–2.4 V/cell, battery) 2.35 V/cell by default (30–42 batteries); 2.3– 2.35 V/cell, 2.35 V/cell by default (44 batteries) ● Float voltage: 2.23–2.3 V/cell, default: 2.25 V/ cell (30–44 batteries) Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 185: Output Electrical Specifications

    ● THDv ≤ 3% (full non-linear load) Output PF Transfer time ● 0 ms (uninterruptible transfer) ● ≤ 20 ms (interruptible transfer) Output voltage unbalance Voltage unbalance: ±3%, phase unbalance: 120±2° Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 186: System Electrical Specifications

    ● Load > 150% or in case of shout circuit, the inverter can work for 200 ms. 8.9 System Electrical Specifications Item Specifications Power distribution system TT, TN-C, TN-S and TN-C-S ECO in a parallel system Supported Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 187: A (Optional) Tn-C System Application

    If the TN-C system is adopted, short-circuit the input N and PE. The recommended cross-sectional area for the cable is 50 mm NO TE The following cable connections are for reference only. Figure A-1 Connecting the input N and PE Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 188: B Alarm List

    UPS5000-E-(30 kVA-120 kVA)-FM User Manual B Alarm List Alarm List NO TE This table lists only common alarms. For more information, contact Huawei technical support. Alarm ID Alarm Name Severity Cause Solution (Alarm ID- Cause ID) 0001-1 Mains voltage Minor ●...
  • Page 189 ● The bypass 2. Check the voltage system input voltage is and bypass voltage not normal. thresholds configured on the LCD. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 190 The battery If the BCB box is configured, voltage reaches check whether the BCB box the EOD voltage trips. If it trips, close the BCB threshold due to box switch. continuous discharge. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 191 ● The charger is 3. If this alarm is generated faulty. in normal mode, check whether the battery switch is ON. If yes, the charger may be faulty. Replace the related power module. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 192 ● The actual number of batteries does not meet requirements. 0036-2 Battery Warning The time for Maintain the batteries. maintenance maintenance reminder arrives. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 193 1. Replace the fan. faulty. 2. Check the fan monitoring 0043-4 ● The fan cable. monitoring cable is faulty. 0047-1 Not ready Critical The ready switch Close the ready switch. is OFF. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 194 ● If all modules generate the alarm, open the bypass input circuit breaker. After the inverter relay is closed, close the bypass input circuit breaker 10 seconds later. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 195 2. Check that the module reduces the power is not derated due rated system to a fan fault. power. 3. If the alarm persists, ● The module is replace the power module. damaged. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 196 ● The intra-rack INVBYP cable is broken. ● The parallel CAN bus is broken. 0584-2 Inter-rack par. Minor The inter-rack Replace the inter-rack parallel cable alarm parallel cable is cable. faulty. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 197 Replace the dry contact board board fault communication MUE05A. with the dry contact board MUE05A fails. 0090-2 Replace the dry contact board communication MUE06A. with the dry contact board MUE06A fails. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 198 The running status is closed circuit breaker is displayed. No further measures are required. 0335 Generator Warning The generator is The running status is connected connected. displayed. No further measures are required. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 199 2. Check that bypass input the bypass and output power cables input or output on each rack meet the cables is length requirements. incorrect. 3. Rectify any bypass SCR ● The bypass SCR open-circuit. open-circuits. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 200 2. After maintenance, open the maintenance circuit breaker and then start the inverter. 0380 In self-check Warning The inverter is in Wait until the inverter self- self-check. check is complete. Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 201: C Acronyms And Abbreviations

    ASIC application-specific integrated circuit American wire gauge bus synchronization controller BCB-BOX battery circuit breaker box BBB-BOX battery bus bar box control area network Conformite Europeenne digital signal processing economic control operation Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 202 Ethernet International Electrotechnical Commission liquid crystal display monitor display unit normally closed normally open negative temperature coefficient power distribution cabinet power distribution unit protective earthing Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.
  • Page 203 THDi total distortion of the input current waveform THDv total harmonic distortion of output voltage uninterruptible power system Universal Serial Bus VRLA valve-regulated lead acid battery Issue 02 (2020-11-10) Copyright © Huawei Technologies Co., Ltd.

This manual is also suitable for:

Ups5000-e-120k-fmUps5000-e-30k-fm