3.2.5.2 Bottom Cable Routing

Context
● There must be sufficient space at the bottom of the cabinet for bottom cable
● If cables need to be routed through holes, remove cable covers for power
● This section describes cable connections when the mains input and bypass
● The figures are for reference only. For more information about the
● Cables are connected in the same way for the 400 kVA, 500 kVA, and 600 kVA
Procedure
Step 1 Open the front door of the cabinet, and remove the front covers of the PDU from
the bypass cabinet.
Step 2 Remove the cable covers from the bottom of the cabinet, drill holes in the covers,
attach grommet strips to the hole edges to protect cables, and reinstall the cable
covers.
The hole size and quantity are for reference only.
Issue 09 (2023-07-10)
NO TICE
routing.
cables from the bypass cabinet and drill holes in the covers. After drilling holes,
attach grommet strips on the hole edges for protecting cables. Reinstall the
covers on the cabinet.
input use different power sources. When they use the same power source, there
is no need to remove the copper bars between the mains and bypass input
terminals or connect the bypass input power cable.
recommended cable cross-sectional area and quantity, refer to
Power Cables
and site requirements.
UPS. This section describes how to connect cables for the 400 kVA UPS. For the
400 kVA cabinet, use M16x50 bolts to connect output, mains input, bypass
input, and battery input cables. For the 500 kVA and 600 kVA cabinets, use
M16x55 bolts to connect output, mains input, bypass input, and battery input
cables. Use M12x35 bolts to connect PE cables.
NO TE
Copyright © Huawei Digital Power Technologies Co., Ltd.
3 Installation
3.1.3 Preparing