UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Step 4 When Intelligent power is set to Enable, the system will automatically modify some
parameter settings which you can view on the corresponding screen.
Figure 5-44 Parameters associated with intelligent power supply 1
Figure 5-45 Parameters associated with intelligent power supply 2
Issue 09 (2019-12-20)
ATS can be set to Connected and Not connected. When it is set to Connected, the UPS
works in the ATS scenario. When it is set to Not connected, the UPS works in the reused
scenario. It is set to Connected by default and is available only when Intelligent power
is set to Enable.
The value range of D.G. startup batt. volt. is 1.80–2.00 V/cell. The default value is 1.80
V/cell. It is available only when Intelligent power is set to Enable.
When the D.G. is connected, ensure that the preceding three parameters have been set so that the UPS
can run properly.