Huawei UPS5000-E Series User Manual page 67

Integrated ups, 50/125 kva
Hide thumbs Also See for UPS5000-E Series:
Table of Contents

Advertisement

UPS5000-E-(50 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
The UPS can generate large leakage currents. A circuit breaker equipped with an RCD is not
recommended.
Table 3-3 Recommended cross-sectional areas for power cables
Item
Input I
Input I current (A)
Recommended circuit
breaker
Recommended
cross-sectional area
2
(mm
)
Input II
Input II current (A)
Recommended circuit
breaker
Recommended
cross-sectional area
2
(mm
)
Battery
Maximum discharge current
(A)
Recommended
cross-sectional area
2
(mm
)
Table 3-4 Recommended cross-sectional areas for output cables
Item
Air conditioner (40 A)
Issue 09 (2019-12-20)
UPS5000-E-1
25K (ATS)
385
Three-pole,
400 A
L1
4 x 185
L2
L3
N
PE
95
385
Three-pole,
400 A
L1
4 x 185
L2
L3
N
PE
95
411
+
2 x 95
N
2 x 95
-
2 x 95
PE
95
L1
Copyright © Huawei Technologies Co., Ltd.
UPS5000-E-1
UPS5000-E-5
25K (MCCB)
0K (ATS)
385
184
Three-pole,
Three-pole,
400 A
250 A
4 x 185
4 x 95
95
50
N/A
184
N/A
Three-pole,
250 A
N/A
4 x 95
50
411
164
2 x 95
95
2 x 95
95
2 x 95
95
95
50
Cable Specifications
5 x 6
3 Installation
UPS5000-E-5
0K (MCCB)
184
Three-pole,
250 A
4 x 95
50
N/A
N/A
N/A
164
95
95
95
50
58