Byte 6: Intermediate Positions - AUMA AUMATIC AC 01.2 Manual

Hide thumbs Also See for AUMATIC AC 01.2:
Table of Contents

Advertisement

Actuator controls
AC 01.2/ACExC 01.2 Modbus RTU
Bit
Designation
(process representation)
2
Fieldb. enable CLOSE
3
4
Fieldbus channel 1
5
Fieldbus channel 2
6
Fieldbus EMCY
7
PVST

Byte 6: Intermediate positions

Table 26: Byte 6: Intermediate positions
Bit
Designation
(process representation)
0
Fieldb. interm. pos. 1
1
Fieldb. interm. pos. 2
2
Fieldb. interm. pos. 3
3
Fieldb. interm. pos. 4
4
Fieldb. interm. pos. 5
5
Fieldb. interm. pos. 6
6
Fieldb. interm. pos. 7
7
Fieldb. interm. pos. 8
Bits 0 7 allow the direct selection of 8 intermediate positions via fieldbus commands.
Hereby the selected intermediate position is approached directly, without stopping
in another intermediate position.
In this case, the actuator continues running until the selected intermediate position
has been reached. Example: Operation from position 5 to 7 without stopping at
position 6.
For further information, please refer to the Manual (operation and setting)AUMATIC
AC 01.2 Modbus.
If the multiport valve function is active (option), the entire byte 6 is used for coding
of multiport valve operation commands. Up to 12 positions can either be approached
selecting the shortest path, in clockwise direction (CW), or in counterclockwise
direction (CCW). Furthermore, the actuator can also be operated without any position
indications (CW or CCW).
Description of the data interface
Value
Description
1
Enabling operation command in direction CLOSE
0
Operation command in direction CLOSE disabled.
No command (reserved)
1
Initiate change-over to channel 1
0
No operation command
1
Initiate change-over to channel 2
0
No operation command
1
EMERGENCY signal, triggers EMERGENCY beha-
viour.
0
No command
1
Start Partial Valve Stroke Test (functional test)
0
No operation command
Value
Description
1
Run to intermediate position 1.
0
No command
1
Run to intermediate position 2.
0
No command
1
Run to intermediate position 3.
0
No command
1
Run to intermediate position 4.
0
No command
1
Run to intermediate position 5.
0
No command
1
Run to intermediate position 6.
0
No command
1
Run to intermediate position 7.
0
No command
1
Run to intermediate position 8.
0
No command
31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aumatic acexc 01.2

Table of Contents