Actuator controls
AC 01.2/ACExC 01.2 Modbus RTU
No.
Type
Parameter
10-3
U16
Trip torque CLO [Nm]
10-4
U16
Trip torque OPEN [Nm]
10-5
I16
Wrn torque CLOSE
10-6
I16
Wrn torque OPEN
Table 42: Local controls
No.
Type
Parameter
Offset (hexadecimal) = 0x04BB
Offset (decimal) = 1211
Data length = 10 bytes
11-1
enum
Self-retaining Local
11-2
enum
Local STOP
11-3
enum
Enable LOCAL
11-4
enum
Priority REMOTE
11-5
enum
Fieldbus auto enable
Table 43: I/O interface
No.
Type
Parameter
Offset (hexadecimal) = 0x04BC
Offset (decimal) = 1212
Data length = 4 bytes
12-1
enum
Self-retaining Remote
12-2
enum
Self-retaining Remote
II
Access
Default
Setting value
R/W
20
Min = 0 [Nm]
Max = 65535 [Nm]
R/W
20
Min = 0 [Nm]
Max = 65535 [Nm]
R/W
80
Min = 20 [%]
Max = 100 [%]
R/W
80
Min = 20 [%]
Max = 100 [%]
Access
Default
Setting value
R/W
3
0 : Off (push-to-run op.)
1 : OPEN
2 : CLOSE
3 : OPEN and CLOSE
4 : OPEN & CL w/o STOP
R/W
0
0 : Off
1 : Sel.sw.Local + Re-
mote
R/W
0
0 : Sel. sw. Local
1 : Sel. sw. Local + Off
R/W
0
0 : Selector switch Local
1 : Sel. sw. Local + Off
R/W
1
0 : Off
1 : On
Access
Default
Setting value
R/W
3
0 : Off (push-to-run op.)
1 : OPEN
2 : CLOSE
3 : OPEN and CLOSE
4 : OPEN & CL w/o STOP
R/W
0
0 : Off (push-to-run op.)
1 : OPEN
2 : CLOSE
3 : OPEN and CLOSE
4 : OPEN & CL w/o STOP
Appendix
Explanation
Tripping torque in direction
CLOSE [Nm]
Tripping torque in direction
OPEN [Nm]
Setting of warning torque in dir-
ection CLOSE
Setting of warning torque in dir-
ection OPEN
Explanation
Setting the self-retaining local
mode
Operation mode local STOP
Operation mode Enable LOCAL
Preserving the operation mode
REMOTE in selector switch pos-
ition LOCAL or OFF depending
on the enable signal
Automatic generation of enable
signal for priority REMOTE
function in case loss of fieldbus
communication
Explanation
Setting the operation behaviour
(push-to-run opereration or self-
retaining) for binary operation
commands (OPEN, STOP,
CLOSE) from remote.
Setting the self-retaining Re-
mote II mode
53