Event Report - AUMA AUMATIC AC 01.2 Manual

Hide thumbs Also See for AUMATIC AC 01.2:
Table of Contents

Advertisement

Appendix
No.
Type
Parameter
60-6
U32
Limit trip CLOSED
60-7
U32
Limit trip OPEN
60-8
U32
Torque trip CLOSE
60-9
U32
Torque trip OPEN
60-10
U32
On time warning 1
60-11
U32
On time warning 2
60-12
U32
System starts
60-13
I32
Max. tem. controls
60-14
I32
Min. temp. controls
60-15
I32
Max. temp. motor
60-16
I32
Min. temp. motor
60-17
I32
Max. temp. gearbox
60-18
I32
Min. temp. gearbox
60-19
I32
Max. temp. MWG
60-20
I32
Min. temp. MWG
60-21
I16
Reset operating data
Table 74: Event report
No.
Type
Parameter
Offset (hexadecimal) = 0x04ED
Offset (decimal) = 1261
Data length = 10 bytes
61-1
U16
File size
61-2
U16
Save interval
61-3
U16
Buffer size
61-4
enum
System event filter
70
Access
Default
Setting value
R
Min = 0 [s]
Max = 4294967295 [s]
R
Min = 0 [s]
Max = 4294967295 [s]
R
Min = 0 [s]
Max = 4294967295 [s]
R
Min = 0 [s]
Max = 4294967295 [s]
R
Min = 0 [s]
Max = 4294967295 [s]
R
Min = 0 [s]
Max = 4294967295 [s]
R
Min = 0 [s]
Max = 4294967295 [s]
R
Min = 100 [°C]
Max = +150 [°C]
R
Min = 100 [°C]
Max = +150 [°C]
R
Min = 100 [°C]
Max = +150 [°C]
R
Min = 100 [°C]
Max = +150 [°C]
R
Min = 100 [°C]
Max = +150 [°C]
R
Min = 100 [°C]
Max = +150 [°C]
R
Min = 100 [°C]
Max = +150 [°C]
R
Min = 100 [°C]
Max = +150 [°C]
R/W
Access
Default
Setting value
R
548
Min = 0
Max = 1024
R
50000
Min = 1000
Max = 65535
R
50
Min = 10
Max = 100
R
31
0 : Commands
1 : Parameterization
2 : Enable processes
3 : System events
4 : Simulation
Actuator controls
AC 01.2/ACExC 01.2 Modbus RTU
Explanation
Number of limit switch CLOSED
trippings
Number of limit switch OPEN
trippings
Number of torque switch
CLOSE trippings
Number of torque switch OPEN
trippings
Total number of all time intervals
during which an on time warning
was indicated.
Max. time span during which an
on time warning was indicated.
Number of AUMATIC system
starts
Maximum temperature of con-
trols
Minimum temperature of con-
trols
Maximum temperature of motor
Minimum temperature of motor
Maximum temperature of gear-
box
Minimum temperature of gear-
box
Maximum temperature of MWG
Minimum temperature of MWG
Deleting operating data
Explanation
File size of event report
Save interval for event data from
buffer
Max. number of events in the
buffer
The event filter for System
defines which system events are
to be recorded into the event
report.