Intermediate Positions; Pivot Points - AUMA PROFOX PF-M25(X) Manual

Hide thumbs Also See for PROFOX PF-M25(X):
Table of Contents

Advertisement

Device menu
Information
Example
4.2.7.

Intermediate positions

Information

4.2.7.1. Pivot points

42
Table 42:
Input signal (DIN) for external speed selection.
Internal speed selection bit 0
0
1
0 = low level (0 V DC or input open)
1 = high level (default: +24 V DC)
The logic for the digital inputs may be inverted. Depending on the parameter (e.g.
PRM_933 Coding DIN 2 for DIN 2), the input is either High active or Low active.
Analogue input
An analogue input (AIN 1 or AIN 2) has to be configured as described to be able to
use an external (analogue) speed setpoint.
DIS_53 Configuration
DIS_139 I/O interface
DIS_389 Analogue inputs
Use analogue input AIN 1 for speed setpoint:
PRM_1129 Signal AIN 1 = Interface speed
With the actuator, up to 8 intermediate positions can be set to any value between 0
% and 100 % of the travel.
When reaching an intermediate position, a signal can be generated and a hysteresis
can be defined for each pivot point.
Currently, this is only possible for pivot points 1 and 2.
DIS_53 Configuration
DIS_143 Intermediate positions
Table 43:
ID
DIS_160
DIS_266
DIS_267
Each of the eight intermediate positions can be set to a value between 0 % and 100
% of the travel.
DIS_53 Configuration
DIS_143 Intermediate positions
DIS_160 Pivot points
Default values:
Pivot point 1 = 15.0 %
Pivot point 2 = 25.0 %
Pivot point 3 = 35.0 %
Pivot point 4 = 45.0 %
Pivot point 5 = 55.0 %
Pivot point 6 = 65.0 %
Pivot point 7 = 75.0 %
Pivot point 8 = 85.0 %
PROFOX actuators
Speed
Motor speed 1
Motor speed 2
Indication
Pivot points
Signal behaviour
Hysteresis