Multi-turn actuators SA 25.1 SA 48.1 SAR 25.1 SAR 30.1 Control unit: electronic (MWG) with actuator controls AC 01.2 Non-Intrusive Control Parallel Profibus DP Profinet Modbus RTU Modbus TCP/IP Foundation Fieldbus HART Operation instructions Assembly, operation, commissioning...
Manual (Operation and setting ) of actuator controls AC 01.2 Modbus Manual (Fieldbus device integration) of actuator controls AC 01.2 Modbus Reference documents can be downloaded from the Internet (www.auma.com) or ordered directly from AUMA (refer to <Addresses>). Table of contents Page Safety instructions.........................
Page 3
Motor connection 5.3.1.1. Motor connection compartment: open 5.3.1.2. Motor cables: connect 5.3.1.3. Motor connection compartment: close 5.3.2. S/SH electrical connection (AUMA plug socket connector) 5.3.2.1. Terminal compartment: open 5.3.2.2. Cable connection 5.3.2.3. Terminal compartment: close 5.4. Accessories for electrical connection 5.4.1.
Page 4
Disposal and recycling Technical data......................... 13.1. Technical data Multi-turn actuators 13.2. Technical data Actuator controls Spare parts..........................14.1. Multi-turn actuators SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 14.2. AC 01.2 actuator controls with SD electrical connection 14.3. Wall bracket Certificates..........................
Any device modification requires prior written consent of the manufacturer. 1.2. Range of application AUMA multi-turn actuators are designed for the operation of industrial valves, e.g. globe valves, gate valves, butterfly valves, and ball valves. Other applications require explicit (written) confirmation by the manufacturer.
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) Safety instructions AC 01.2 Non-Intrusive Modbus RTU Lifting appliances according to EN 14502 Passenger lifts according to DIN 15306 and 15309 Service lifts according to EN 81-1/A1 Escalators Continuous duty...
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Modbus RTU Safety instructions 1.4. Warnings and notes The following warnings draw special attention to safety-relevant procedures in these operation instructions, each marked by the appropriate signal word (DANGER, WARNING, CAUTION, NOTICE).
(push buttons and display) and perform settings (contents of these instructions). read in or out data or modify and save settings via AUMA CDT software (ac- cessory), using a computer (laptop or PC). The connection between computer and actuator controls is wireless via Bluetooth interface (not included in these instructions).
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Modbus RTU Identification 2.2. Name plate Figure 3: Arrangement of name plates Actuator name plate Actuator controls name plate Motor name plate Additional plate, e.g. KKS plate (Power Plant Classification System)
Page 10
Figure 5: Name plate for actuator controls (example) Type designation Order number Serial number Actuator terminal plan Actuator controls terminal plan Mains voltage AUMA power class for switchgear Permissible ambient temperature Enclosure protection [10] Control [11] Data Matrix code Motor name plate Figure 6: Motor name plate (example) (= manufacturer logo);...
Page 11
The rated power (nominal power) of the actuator motor is indicated in kW on the motor name plate. For the assignment of the AUMA power classes to the nominal power of the motor types, refer to the separate electrical data sheets.
Page 12
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) Identification AC 01.2 Non-Intrusive Modbus RTU Figure 8: Link to AUMA Assistant App: For further Service & Support, software/apps/... refer to www.auma.com.
Weight for AC 01.2 actuator controls with electrical connection type: Weight approx. [kg] AUMA plug/socket connector with screw-type connection Table 5: Weights for multi-turn actuators SA 25.1 SA 48.1 / SAR 25.1 SAR 30.1 with 3-phase AC motors Type designation...
SA 48.1 AD... 180-... Refer to motor name plate Indicated weight includes AUMA NORM multi-turn actuator with 3-phase AC motor, electrical con- nection in standard version, output drive type B1 and handwheel. For other output drive types, heed additional weights.
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Modbus RTU Assembly Assembly 4.1. Mounting position The product described in this document can be operated without restriction in any mounting position. 4.2. Handwheel fitting Information For transport reason, handwheels with a diameter of 400 mm and larger are supplied separately within the scope of delivery.
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) Assembly AC 01.2 Non-Intrusive Modbus RTU Secure handwheel using the retaining ring supplied. Figure 12: 4.3. Multi-turn actuator: mount to valve/gearbox Danger of corrosion due to damage to paint finish and condensation! Touch up damage to paint finish after work on the device.
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Modbus RTU Assembly 4.3.1.1. Stem nut: finish machining This working step is only required if stem nut is supplied unbored or with pilot bore. Figure 14: Output drive type A...
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) Assembly AC 01.2 Non-Intrusive Modbus RTU 4.3.1.2. Multi-turn actuator (with output drive type A): mount to valve Figure 15: Assembly of output drive type A Valve stem Output drive type A...
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Modbus RTU Assembly 4.3.2. Output drive types B and E For rotating, non-rising valve stem Application Not capable of withstanding thrust For output drive types B/B1/B2, the connection to the valve or the gearbox is made...
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) Assembly AC 01.2 Non-Intrusive Modbus RTU Check if output drive of multi-turn actuator [1] matches the output drive of valve/gearbox or valve/gearbox valve shaft [2/3]. Apply a small quantity of grease to the valve or gearbox shaft [3].
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Modbus RTU Assembly Screw stem protection tube [2] into thread and tighten it firmly. Information: For stem protection tubes made of two or more segments, all parts have to be thoroughly screwed together.
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) Assembly AC 01.2 Non-Intrusive Modbus RTU 4.5.1. Mounting positions: modify Hazardous voltage! Risk of electric shock. Disconnect device from the mains before opening. Electrostatic discharge ESD! Risk of damage to electronic components.
The pertaining wiring diagram/terminal plan (in German or English) is attached to the device in a weather-proof bag, together with these operation instructions. It can plan also be requested from AUMA (state order number, refer to name plate) or downloaded directly from the Internet (http://www.auma.com). Permissible networks Actuator controls (actuators) are suitable for use in TN and TT networks with directly earthed star point for mains voltage up to maximum 690 V AC.
Page 24
Thyristor B3 up to 5.5 kW 63 A (g/R) I²t<5,000A²s The AUMA power class (A1, B1, ...) is indicated on the actuator controls name plate Consider the motor starting current (I ) (refer to electrical data sheet) when selecting the circuit breaker. We recommend tripping characteristics D or K for circuit breakers in accordance with IEC 60947-2.
Page 25
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Modbus RTU Electrical connection The interference immunity of signal and fieldbus cables increases if the cables are laid close to the earth potential. If possible, avoid laying long cables and make sure that they are installed in areas being subject to low interference.
Short description Control contacts also available as crimp-type connection as an option. SD version. For power and control cable connection, remove the AUMA plug/socket connector and the socket carrier from terminal compartment. Removing the cover is sufficient for connecting the fieldbus cables.
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Modbus RTU Electrical connection 5.2.1.1. Terminal compartment (for mains connection): open Figure 23: Open mains terminal compartment Connection housing Screws for frame O-ring Screws for socket carrier...
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Modbus RTU Electrical connection 5.2.1.3. Terminal compartment (for mains connection): close Figure 26: Close mains terminal compartment Connection housing Screws for connection housing O-ring Screws for socket carrier...
Screws for cover O-ring Cable entries for fieldbus cables Blanking plug The AUMA plug/socket connector is equipped with a connection board for connecting the fieldbus cables. When removing the cover [1], the connection board is easily accessible. Hazardous voltage! Risk of electric shock.
For loop redundancy, automatic termination is performed as soon as actuator controls are connected to the power supply. When interrupting the power supply, e.g. after removing the AUMA plug/socket connector, both RS-485 loop segments are automatically connected to each other.
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) Electrical connection AC 01.2 Non-Intrusive Modbus RTU If the actuator is the final fieldbus device in the fieldbus segment: 2.1 Switch on the termination resistor for channel 1 using switch [S1] (position ON).
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Modbus RTU Electrical connection 5.3. Electrical connection of actuator Figure 31: Connection arrangement for sizes 25.1 40.1 Motor connection compartment for nominal currents exceeding 25 A...
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) Electrical connection AC 01.2 Non-Intrusive Modbus RTU 5.3.1. Motor connection 5.3.1.1. Motor connection compartment: open Figure 33: Motor connection compartment: open Cover Screws for cover O-ring Cable gland Hazardous voltage! Risk of electric shock.
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Modbus RTU Electrical connection Terminal cross sections and terminal tightening torques Type Speed Terminal cross sections Tightening torques SA 40.1 35 mm 5.0 Nm 70 mm 12 Nm SA 48.1...
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) Electrical connection AC 01.2 Non-Intrusive Modbus RTU 5.3.2.3. Terminal compartment: close Figure 39: Terminal compartment: close Cover (figure shows S version) Screws for cover O-ring Screws for socket carrier...
The permissible cable length between actuator controls on wall bracket and the actuator amounts to 100 m maximum. We recommend using an AUMA “LSW” cable set . If the AUMA cable set is not used: Use suitable flexible and screened connecting cables.
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) Electrical connection AC 01.2 Non-Intrusive Modbus RTU When using connecting cables, e.g. of the heater or switch, requiring direct wiring from the actuator to the XK customer plug (XA-XM-XK, refer to wiring diagram), these connecting cables must be subject to an insulation test in compliance with EN 50178.
Page 41
Motor connection/motor control Feedback signals from actuator For actuators with high nominal motor current (AUMA power class switchgear from category A4), a control box is required. Switchgear (reversing contactors) will then be installed in the control box and not within the actuator controls. The control box is mounted separately on a wall.
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) Electrical connection AC 01.2 Non-Intrusive Modbus RTU 5.4.3. Parking frame Figure 43: Parking frame, example with plug/socket connector and cover Parking frame for safe storage of a disconnected plug or cover.
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) Operation AC 01.2 Non-Intrusive Modbus RTU Operation 6.1. Manual operation For purposes of setting and commissioning, in case of motor or power failure, the actuator may be operated manually. Manual operation is engaged by an internal change-over mechanism.
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Modbus RTU Operation Turn handwheel in desired direction. To close the valve, turn handwheel clockwise: Drive shaft (valve) turns clockwise in direction CLOSE. Figure 48: 6.1.2.
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) Operation AC 01.2 Non-Intrusive Modbus RTU Hot surfaces, e.g. possibly caused by high ambient temperatures or strong direct sunlight! Danger of burns Verify surface temperature and wear protective gloves.
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Modbus RTU Operation Figure 50: [1 4] Push buttons or navigation support Selector switch Display Table 22: Important push button functions for menu navigation Push buttons...
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) Operation AC 01.2 Non-Intrusive Modbus RTU Figure 52: Marking with ID ID starts with = status menu ID starts with = main menu It is possible to select between status menu S and main menu M: Group selection For this, set selector switch to 0 (OFF), hold down push button C for approx.
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) Operation AC 01.2 Non-Intrusive Modbus RTU Select parameter Change passwords either: Change passwords click via the menu to parameter, or via direct display: press and enter ID M0229 Display indicates: ▶ Change passwords The user level is indicated in the top row (1 6), e.g.:...
Page 51
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Modbus RTU Operation Enter password (→ enter password). Display indicates: ▶ Language and Save (bottom row) Language selection 10. Select new language via Up ▲ Down ▼ resulting in the following significations: black triangle: ▶...
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) Indications AC 01.2 Non-Intrusive Modbus RTU Indications 7.1. Indications during commissioning When switching on the power supply, all LEDs on the local controls illuminate for LED test approx. 1 second. This optical feedback indicates that the voltage supply is connected to the controls and all LEDs are operable.
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Modbus RTU Indications Figure 60: Information in the status bar (top) Operation mode Error symbol (only for faults and warnings) ID number: S = Status page...
Page 54
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) Indications AC 01.2 Non-Intrusive Modbus RTU Figure 64: Torque allows to select the unit displayed (percent %, Newton metre Nm Select unit The push button or "foot-pound" ft-lb Figure 65: Units of torque 100 % indication equals the max.
Pause for operation in direction OPEN Pause for operation in directions OPEN and CLOSE 7.2.2. Status indications according to AUMA classification These indications are available if the parameter Diagnostic classific. M0539 is set to AUMA. Warnings (S0005) If a warning has occurred, the display shows S0005: the number of warnings occurred a blinking question mark after approx.
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) Indications AC 01.2 Non-Intrusive Modbus RTU Not ready REMOTE (S0006) The S0006 display shows indications of the Not ready REMOTE group. If such an indication has occurred, the display shows S0006: the number of indications occurred a blinking crossbar after approx.
Page 57
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Modbus RTU Indications Figure 73: Function check For further information, please also refer to <Corrective action>. Maintenance required (S0010) The S0010 indication shows maintenance indications according to NAMUR recommendation NE 107.
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) Indications AC 01.2 Non-Intrusive Modbus RTU 7.3. Indication lights of local controls Figure 76: Arrangement and signification of indication lights Marking with symbols (standard) Marking with figures 1 6 (option)
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Modbus RTU Indications 7.4. Optional indications 7.4.1. Mechanical position indication (self-adjusting) Figure 77: Mechanical position indicator End position OPEN reached End position CLOSED reached Independent of power supply...
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) Signals (output signals) AC 01.2 Non-Intrusive Modbus RTU Signals (output signals) 8.1. Status signals via output contacts (digital outputs) Output contacts are only available if a parallel interface is provided in addition to the Conditions fieldbus interface.
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Modbus RTU Commissioning (basic settings) Commissioning (basic settings) Set selector switch to position 0 (OFF). Information: The selector switch is not a mains switch. When positioned to 0 (OFF), the actuator cannot be operated.
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) Commissioning (basic settings) AC 01.2 Non-Intrusive Modbus RTU Up ▲ Down ▼ to select user: User login Information: Required user level: Specialist (4) or higher The symbols have the following meaning: black triangle: ▶...
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Modbus RTU Commissioning (basic settings) Press Display shows the set value. The bottom row indicates: Edit Esc Edit. Press Display indicates: Specialist (4) → continue with step 7 in bottom row Up ▲...
Page 64
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) Commissioning (basic settings) AC 01.2 Non-Intrusive Modbus RTU Limit switching M0010 Set end pos.CLOSED? M0084 Set end pos. OPEN? M0085 Set selector switch to position 0 (OFF). Select main menu Press push button C and hold it down for approx.
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Modbus RTU Commissioning (basic settings) 10. Press Yes to confirm new end position. Confirm new end posi- tion Display indicates: End pos. CLOSED set! The left LED is illuminated (standard version) and thus indicates that the end position CLOSED setting is complete.
SAR 30.1 Control unit: electronic (MWG) Commissioning (basic settings) AC 01.2 Non-Intrusive Modbus RTU Information Parameter MD2 slave address is only available if AUMA redundancy I (option) is available. For further settings and information e.g. on redundancy, refer to Manual (Device integration).
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Modbus RTU Commissioning (basic settings) Switch on actuator in direction CLOSE and observe the direction of rotation on the mechanical position indication: For self-adjusting mechanical position indication:...
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) Commissioning (basic settings) AC 01.2 Non-Intrusive Modbus RTU Switch on actuator in direction CLOSE and observe direction of rotation at hollow shaft [3] or stem [5]: The direction of rotation is correct if the actuator moves in direction CLOSE and the hollow shaft in clockwise direction, or the stem moves downward.
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Modbus RTU Commissioning (settings/options in the actuator) Commissioning (settings/options in the actuator) For actuators without mechanical position indicator (cover without indicator glass), no settings are required within the actuator when commissioning.
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) Commissioning (settings/options in the actuator) AC 01.2 Non-Intrusive Modbus RTU Open Loosen screws [2] and remove cover [1] from the switch compartment. Open Clean sealing faces of housing and cover.
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Modbus RTU Commissioning (settings/options in the actuator) Move actuator to end position OPEN. The arrow rotates in direction OPEN driving the indicator disc with symbol (OPEN) until the actuator stops in position OPEN.
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) Commissioning (settings/options in the actuator) AC 01.2 Non-Intrusive Modbus RTU To modify settings, lift the lever at the reduction gearing and engage at the se- lected stage. Figure 88: Set reduction gearing 10.3.
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Modbus RTU Commissioning (settings/options in the actuator) Move valve to end position CLOSED again. Check settings: If the symbol (CLOSED) is no longer in alignment with mark on the cover: 6.1 Repeat setting procedure.
Page 74
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) Commissioning (settings/options in the actuator) AC 01.2 Non-Intrusive Modbus RTU Loosen screw [1]. Set crown wheel [2] to desired level according to table. Tighten screw [1]. Place indicator disc on shaft.
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Modbus RTU Corrective action Corrective action 11.1. Faults during commissioning Table 28: Faults during operation/commissioning Fault Description/cause Remedy Mechanical position indicator cannot Reduction gearing is not suitable for turns/stroke Set gear stage of the reduction gearing.
Page 76
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) Corrective action AC 01.2 Non-Intrusive Modbus RTU Table 30: Warnings and Out of specification Indication on display Description/cause Remedy Config. warning Collective signal 06: Press push button Details to display a list of indi- Possible cause: vidual indications.
Page 77
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Modbus RTU Corrective action Warnings and Out of specification Indication on display Description/cause Remedy PVST required Execution of PVST (Partial Valve Stroke Tests) is required. Maintenance required Maintenance is required.
Page 78
Selector switch is not in position REMOTE. Set selector switch to position REMOTE. Service active Operation via service interface (Bluetooth) and Exit service software. AUMA CDT service software. Disabled Actuator is in operation mode Disabled. Check setting and status of function <Local controls enable>.
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Modbus RTU Corrective action Not ready REMOTE and Function check (collective signal 04) Indication on display Description/cause Remedy EMCY behav. active Operation mode EMERGENCY is active (EMER- Detect cause for EMERGENCY signal.
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) Corrective action AC 01.2 Non-Intrusive Modbus RTU 11.3.2. Fuse replacement 11.3.2.1. Replace fuses F1/F2. Hazardous voltage! Risk of electric shock. Disconnect device from the mains before opening. Remove electrical connection from actuator controls.
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Modbus RTU Corrective action To replace defective fuses: Carefully loosen power supply unit [3] and pull out. (The fuses are on the equipped part of the power supply board.) Cable damage due to pinching! Risk of functional failures.
Therefore, we recommend contacting our service. Only perform servicing and maintenance tasks when the device is switched off. AUMA AUMA offers extensive service such as servicing and maintenance as well as Service & Support customer product training. For the relevant contact addresses, please refer to <Addresses>...
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Modbus RTU Servicing and maintenance 12.2. Maintenance Lubrication In the factory, the gear housing is filled with grease. Grease change is performed during maintenance Generally after 4 to 6 years for modulating duty.
22 rpm (50 Hz) or 26 (60 Hz) NOT self-locking: SA 25.1 and SA 30.1 for output speeds from 125 rpm (50Hz) or 150 rpm (60Hz) and from size SA 35.1 for output speeds from 32 rpm (50Hz) or 38 (60Hz).
Page 85
Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength may not be derived from this. Indiations apply to actuators with AUMA 3-phase AC motor and AUMA plug/socket connector. They are not valid in combination with gearboxes.
The reversing contactors are designed for a lifetime of 2 million starts. For applications requiring a high number of starts, we recommend the use of thyristor units. For the assignment of AUMA power classes, please refer to Electrical data on actuator Control and feedback signals...
Page 87
(Not possible in combination with PTC tripping device) Redundancy (option) Redundant line topology with universal redundancy behaviour according to AUMA redundancy I or II Redundant loop topology in combination with SIMA Master Station Max. number of actuators with actuator controls per redundant loop: 247 units Max.
Page 88
Communication interface Required accessories: AUMA CDT (Commissioning and Diagnostic Tool for Windows-based PC) AUMA Assistant App (Commissioning and Diagnostic Tool for Android devices) Application functions Standard: Selectable type of seating, limit or torque seating for end position OPEN and end po-...
Page 89
Overvoltage protection (option) Protection of the actuator and control electronics against overvoltages on the fieldbus cables of up to 4 Electrical connection Standard: AUMA plug/socket connector with screw-type connection Option: Gold-plated control plug (sockets and plugs) Threads for cable entries...
Page 90
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) Technical data AC 01.2 Non-Intrusive Modbus RTU General data of the Modbus RTU interface Number of devices 32 devices in each segment without repeater, with repeaters expandable to 247...
Page 91
Terminal compartment additionally sealed against interior of actuator controls (double sealed) According to AUMA definition, enclosure protection IP68 meets the following requirements: Depth of water: Maximum 8 m head of water Duration of continuous immersion in water: Maximum 96 hours Up to 10 operations during continuous immersion Modulating duty is not possible during continuous immersion.
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) Spare parts AC 01.2 Non-Intrusive Modbus RTU Spare parts 14.1. Multi-turn actuators SA 25.1 SA 48.1/SAR 25.1 SAR 30.1...
Page 93
Spare parts Please state device type and our order number (see name plate) when ordering spare parts. Only original AUMA spare parts should be used. Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Representation of spare parts may slightly vary from actual delivery.
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) Spare parts AC 01.2 Non-Intrusive Modbus RTU 14.2. AC 01.2 actuator controls with SD electrical connection...
Page 95
Spare parts Please state device type and our order number (see name plate) when ordering spare parts. Only original AUMA spare parts should be used. Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Representation of spare parts may slightly vary from actual delivery.
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) Spare parts AC 01.2 Non-Intrusive Modbus RTU 14.3. Wall bracket...
Page 97
Spare parts Please state device type and our order number (see name plate) when ordering spare parts. Only original AUMA spare parts should be used. Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Representation of spare parts may slightly vary from actual delivery.
Certificates are valid as from the indicated date of issue. Subject to changes without Information notice. The latest versions are attached to the device upon delivery and also available for download at http://www.auma.com. 15.1. EU Declaration of Incorporation / Declaration of Conformity...
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Modbus RTU Index Index Earth connection Electrical connection Accessories (electrical con- Enclosure protection 9, 10, 10, 85, 91 nection) Error - indication on display Accessories for assembly...
Page 100
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) Index AC 01.2 Non-Intrusive Modbus RTU Main menu Range of application Mains frequency 10, 10 Rated current Mains voltage 10, 10, 23 Rated power Maintenance 5, 82, 83 Recycling...
Page 101
SA 25.1 SA 48.1/SAR 25.1 SAR 30.1 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Modbus RTU Index Valve position - indication on display Valve stem Vibration resistance Voltage range Wall bracket 39, 40 Warnings - indication on dis- play Wire diameter (fieldbus cable)
Europe AUMA Finland Oy AUMA-LUSA Representative Office, Lda. FI 02230 Espoo PT 2730-033 Barcarena Tel +358 9 5840 22 Tel +351 211 307 100 AUMA Riester GmbH & Co. KG auma@auma.fi geral@aumalusa.pt www.auma.fi Location Muellheim SAUTECH DE 79373 Muellheim AUMA France S.A.R.L.
Page 103
AUMA worldwide America AUMA Actuators (China) Co., Ltd. FLOWTORK TECHNOLOGIES CN 215499 Taicang CORPORATION AUMA Argentina Rep.Office Tel +86 512 3302 6900 PH 1550 Mandaluyong City AR Buenos Aires mailbox@auma-china.com Tel +63 2 532 4058 Tel +54 11 4737 9026 www.auma-china.com...
Page 104
AUMA Riester GmbH & Co. KG P.O. Box 1362 DE 79373 Muellheim Tel +49 7631 809 - 0 Fax +49 7631 809 - 1250 info@auma.com www.auma.com Y005.668/003/en/1.18 For detailed information on AUMA products, refer to the Internet: www.auma.com...
Need help?
Do you have a question about the SA 25.1 and is the answer not in the manual?
Questions and answers