Byte 24: Maintenance Required; Byte 25: Out Of Specification 1; Byte 26: Out Of Specification 2 - AUMA AUMATIC AC 01.2 Manual

Hide thumbs Also See for AUMATIC AC 01.2:
Table of Contents

Advertisement

Actuator controls
AC 01.2/ACExC 01.2 Modbus RTU
Table 16: Byte 24: Maintenance required
Bit
Designation
(process representation)
0
Bit: Maintenance mechan-
ics
1
Bit: Maintenance seals
2
Bit: Maintenance lubricant
3
Bit: Maintenance contact-
ors
4
Bit: Maintenance interval
5
6
7
Table 17: Byte 25: Out of specification 1
Bit
Designation
(process representation)
0
1
2
3
4
Bit: Torque warn. CLOSE
5
Bit: Torque warn. OPEN
1)
6
Bit: SIL fault
7
Bit: No reaction
1)
The safety function indications via fieldbus are for information only and must not be used as part of a safety function. The I/O signals of
the SIL module must be used for this purpose.
Table 18: Byte 26: Out of specification 2
Bit
Designation
(process representation)
0
Bit: Wrn controls temp
1
2
3
Bit: 24 V DC, external
4
5
Bit: RTC button cell
Value
Description
1
Mechanic maintenance requirement
0
No signal
1
Seal maintenance requirement
0
No signal
1
Lubricant maintenance requirement
0
No signal
1
Contactor maintenance requirement
0
No signal
1
The set maintenance interval has expired.
0
No signal
No signal (reserved)
No signal (reserved)
No signal (reserved)

Byte 25: Out of specification 1

Causes of the Out of specification signal in accordance with NAMUR recommendation
NE 107.
Value
Description
No signal (reserved)
No signal (reserved)
No signal (reserved)
No signal (reserved)
1
Warning: Limit value for torque warning in direction CLOSE exceeded.
0
No signal
1
Warning: Limit value for torque warning in direction OPEN exceeded.
0
No signal
1
Warning: A SIL fault of the SIL sub-assembly has occurred.
0
No signal
1
Warning: No actuator reaction to operation commands within the set reaction time.
0
No signal

Byte 26: Out of specification 2

Value
Description
1
Warning: Temperature within controls housing too high
0
No signal
No signal (reserved)
No signal (reserved)
1
The external 24 V AC voltage supply of the controls has exceeded the power supply
limits.
0
No signal
No signal (reserved)
1
Warning: The voltage of the RTC button cell is too low.
0
No signal
Description of the data interface