Appendix
No.
Type
Parameter
16-3
enum
EMCY failure source
16-4
enum
EMCY operation
16-5
U16
EMCY position
16-6
enum
By-pass torque
16-7
enum
Thermal by-pass
16-8
enum
By-pass timer
16-9
enum
By-pass operat.profile
16-10
enum
By-pass Interlock
16-11
enum
By-pass Local STOP
16-12
Mmss01
Delay time
16-13
U16
EMCY position MPV
Table 48: Timer function
No.
Type
Parameter
Offset (hexadecimal) = 0x04C1
Offset (decimal) = 1217
Data length = 20 bytes
17-1
enum
Step mode CLOSE
17-2
Mmss01
On time CLOSE
17-3
Mmss01
Off time CLOSE
17-4
U16
Start stepping CLOSE
17-5
U16
End stepping CLOSE
17-6
enum
Step mode OPEN
56
Access
Default
Setting value
R/W
3
1 : I/O interface
2 : Fieldbus interface
3 : I/O or fieldbus
4 : Active interface
R/W
0
0 : STOP
1 : CLOSE
2 : OPEN
3 : Approach EMCY pos.
R/W
0
Min = 0 [0.1 %]
Max = 1000 [0.1 %]
R/W
0
0 : Off
1 : On
R/W
0
0 : Off
1 : On
R/W
0
0 : Off
1 : On
R/W
0
0 : Off
1 : On
R/W
0
0 : Off
1 : On
R/W
0
0 : Off
1 : On
R
10
Min = 0 [0.1 s]
Max = 1800 [0.1 s]
R/W
10
Min = 0 [0.1 s]
Max = 1800 [0.1 s]
Access
Default
Setting value
R/W
0
0 : Off
1 : Remote
2 : Local
3 : Remote and local
R/W
50
Min = 10 [0.1 s]
Max = 1800 [0.1 s]
R/W
50
Min = 10 [0.1 s]
Max = 1800 [0.1 s]
R/W
1000
Min = 1 [0.1 %]
Max = 1000 [0.1 %]
R/W
0
Min = 0 [0.1 %]
Max = 999 [0.1 %]
R/W
0
0 : Off
1 : Remote
2 : Local
3 : Remote and local
Actuator controls
AC 01.2/ACExC 01.2 Modbus RTU
Explanation
Failure source for EMERGENCY
behaviour
Actuator reaction in EMER-
GENCY operation mode
Setting the EMERGENCY posi-
tion
By-passing the torque monitor-
ing in EMERGENCY operation
mode
By-passing the thermal monitor-
ing in EMERGENCY operation
mode
By-passing the timer function in
EMERGENCY operation mode
By-pass of operation profile in
EMERGENCY operation mode
By-pass of interlock function in
operation mode EMERGENCY
By-pass of local STOP function
in EMERGENCY operation
mode
Delay time for EMERGENCY
behaviour (EMERGENCY beha-
viour is only executed after the
delay time has expired).
EMERGENCY position of multi-
port valve
Explanation
Setting the operation mode:
Stepping mode in direction
CLOSE
Setting the on time in direction
CLOSE
Setting the off time in direction
CLOSE
Setting the start of stepping
mode in direction CLOSE
Setting the end of stepping
mode in direction CLOSE
Setting the operation mode:
Stepping mode in direction
OPEN