No.
Type
Parameter
38-3
U16
Low limit Uspan
38-4
U16
Hysteresis
Table 60: Phase failure monitoring
No.
Type
Parameter
Offset (hexadecimal) = 0x04D7
Offset (decimal) = 1239
Data length = 4 bytes
39-1
enum
Adapt rotary dir.
39-2
U16
Tripping time
Table 61: Switchgear
No.
Type
Parameter
Offset (hexadecimal) = 0x04D8
Offset (decimal) = 1240
Data length = 2 bytes
40-1
U16
Revers. prevent. time
Table 62: Monitoring functions
No.
Type
Parameter
Offset (hexadecimal) = 0x04D9
Offset (decimal) = 1241
Data length = 18 bytes
41-1
enum
Monitor heat. system
41-2
enum
Monitor 24 V DC ext.
41-3
enum
Monitor 24 V DC cust.
41-4
enum
Monitor 24 V AC
41-5
enum
Monitor 24 V DC intern
41-6
enum
PTC trip. monit.
64
Access
Default
Setting value
R/W
610
Min = 0
Max = 1023
R
2
Min = 0
Max = 10
Access
Default
Setting value
R
1
0 : Function not active
1 : Function active
R/W
100
Min = 20 [0.1 s]
Max = 3000 [0.1 s]
Access
Default
Setting value
R
3
Min = 1 [0.1 s]
Max = 300 [0.1 s]
Access
Default
Setting value
R
0
0 : Function not active
1 : Function active
R
0
0 : Function not active
1 : Function active
R/W
1
0 : Function not active
1 : Function active
R
1
0 : Function not active
1 : Function active
R
1
0 : Function not active
1 : Function active
R
0
0 : Function not active
1 : Function active
Actuator controls
AC 01.2/ACExC 01.2 Modbus RTU
Explanation
Low limit setting of potentiomet-
er signal range (monitoring the
potentiometer span)
Hysteresis of potentiometer
Explanation
Adapt rotary direction for coun-
terclockwise rotating field
Duration until phase monitoring
trips
Explanation
Setting the reversing prevention
time
Explanation
Monitoring the heating system
in the AC
Monitoring external 24 V DC
(external supply)
Monitoring 24 V DC for custom-
er (control voltage)
Monitoring 24 V AC
Monitoring internal 24 V DC
PTC tripping device monitoring