AC 01.2/ACExC 01.2 Modbus RTU
Table 21: Byte 29: Function check 1
Bit
Designation
(process representation)
0
Bit: Local STOP
1
Bit: Sel. sw. not REMOTE
2
Bit: Service active
3
Bit: Handwheel active
4
Bit: EMCY stop active
5
Bit: PVST active
6
7
Table 22: Byte 31: Status Feldbus
Bit
Designation
(process representation)
0
Bit: Channel 1 active
1
Bit: Channel 2 active
2
Bit: Channel 1 DataEx
3
Bit: Channel 2 DataEx
4
Bit: Chan 1 FailState field-
bus
5
Bit: Chan 2 FailState field-
bus
6
Bit: Channel 1 activity
7
Bit: Channel 2 activity

Byte 29: Function check 1

Causes of the Function check signal in accordance with NAMUR recommendation
NE 107.
Value
Description
1
Push button STOP of the local controls is operated.
0
No signal
1
Selector switch is in position Local control (LOCAL) or 0 (OFF).
0
Selector switch is in position Remote control (REMOTE).
1
Operation mode Service is active.
0
No signal
1
Manual operation is active (handwheel is engaged); optional indication
0
No signal
1
Operation mode EMERGENCY stop is active (EMERGENCY stop button has been
pressed).
0
EMERGENCY stop button not pressed (normal operation).
1
Partial Valve Stroke Test function (PVST) is active.
0
No signal
No signal (reserved)
No signal (reserved)
Byte 30: Function check 2
The contents are reserved for further Function check signals in accordance with
NAMUR recommendation NE 107.

Byte 31: Fieldbus status

Information on the fieldbus status.
Value
Description
1
Channel 1 is the active operation command channel.
0
No signal
1
Channel 2 is the active operation command channel.
0
No signal
1
Channel 1 is in the data exchange state.
0
No signal
1
Channel 2 is in the data exchange state.
0
No signal
1
No valid fieldbus communication via channel 1 (application does not communicate
with the DCS).
0
No signal
1
No valid fieldbus communication via channel 2 (application does not communicate
with the DCS).
0
No signal
1
Bus communication available on channel 1.
0
No signal
1
Bus communication available on channel 2.
0
No signal

Byte 32: SIL indications

Detailed information of an optional SIL sub-assembly.
Description of the data interface