Operation Commands Via Byte 6 For Activated Multiport Valve Function - AUMA AUMATIC AC 01.2 Manual

Hide thumbs Also See for AUMATIC AC 01.2:
Table of Contents

Advertisement

Description of the data interface
32
Table 27: Operation commands via byte 6 for activated multiport valve function
Value
≙ Operation direction/posi-
tion
0x01
Position 1
0x02
Position 2
0x04
Position 3
0x08
Position 4
0x10
Position 5
0x20
Position 6
0x40
Position 7
0x80
Position 8
0x81
Position 9
0x82
Position 10
0x83
Position 11
0x84
Position 12
0x90
CW
0x91
CW Position 1
0x92
CW Position 2
0x93
CW Position 3
0x94
CW Position 4
0x95
CW Position 5
0x96
CW Position 6
0x97
CW Position 7
0x98
CW Position 8
0x99
CW Position 9
0x9A
CW Position 10
0x9B
CW Position 11
0x9C
CW Position 12
0xA0
CCW
0xA1
CCW Position 1
0xA2
CCW Position 2
0xA3
CCW Position 3
0xA4
CCW Position 4
0xA5
CCW Position 5
0xA6
CCW Position 6
AC 01.2/ACExC 01.2 Modbus RTU
Behaviour
Position 1 is approached selecting the shortest path
Position 2 is approached selecting the shortest path
Position 3 is approached selecting the shortest path
Position 4 is approached selecting the shortest path
Position 5 is approached selecting the shortest path
Position 6 is approached selecting the shortest path
Position 7 is approached selecting the shortest path
Position 8 is approached selecting the shortest path
Position 9 is approached selecting the shortest path
Position 10 is approached selecting the shortest
path
Position 11 is approached selecting the shortest
path
Position 12 is approached selecting the shortest
path
Actuator operates in clockwise direction (without
stop at any position)
Position 1 is approached in clockwise direction
(CW).
Position 2 is approached in clockwise direction
(CW).
Position 3 is approached in clockwise direction
(CW).
Position 4 is approached in clockwise direction
(CW).
Position 5 is approached in clockwise direction
(CW).
Position 6 is approached in clockwise direction
(CW).
Position 7 is approached in clockwise direction
(CW).
Position 8 is approached in clockwise direction
(CW).
Position 9 is approached in clockwise direction
(CW).
Position 10 is approached in clockwise direction
(CW).
Position 11 is approached in clockwise direction
(CW).
Position 12 is approached in clockwise direction
(CW).
Actuator operation in counterclockwise direction
(without stop at any position)
Position 1 is approached in counterclockwise direc-
tion (CCW).
Position 2 is approached in counterclockwise direc-
tion (CCW).
Position 3 is approached in counterclockwise direc-
tion (CCW).
Position 4 is approached in counterclockwise direc-
tion (CCW).
Position 5 is approached in counterclockwise direc-
tion (CCW).
Position 6 is approached in counterclockwise direc-
tion (CCW).
Actuator controls

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aumatic acexc 01.2

Table of Contents