Byte 5: Device Status - AUMA AUMATIC AC 01.2 Manual

Hide thumbs Also See for AUMATIC AC 01.2:
Table of Contents

Advertisement

Description of the data interface
Bit
Designation
(process representation)
6
Bit: Torque sw.OPEN
7
Bit: Torque sw.CLOSE
Table 3: Byte 5: Device status
Bit
Designation
(process representation)
0
Bit: Not ready REMOTE
1
Bit: Warnings
2
Bit: Fault
3
Bit: Maintenance requ.
4
Bit: Out of spec.
5
Bit: Function check
6
Bit: Failure
7
Bit: Device ok
14
Value
Description
1
Torque switch operated in direction OPEN.
0
No signal
1
Torque switch operated in direction CLOSE.
0
No signal
Bytes 3 and 4: Actual position
Byte 3 = high byte, byte 4 = low byte.
If a position transmitter (potentiometer, RWG, EWG, or MWG) is installed in the
actuator, bytes 3 and 4 are used to transmit the current actuator position. The value
is transmitted in per mil (value: 0

Byte 5: Device status

Value
Description
1
Collective signal 04:
Contains the result of a disjunction (OR-operation) of all bits comprised in bytes 13
and 14 (Not ready REMOTE 1 and Not ready REMOTE 2).
The actuator cannot be operated from REMOTE.
The actuator can only be operated via the local controls.
0
In bytes 13 and 14, no signals are active (all bits are set to 0).
1
Collective signal 02:
Contains the result of a disjunction (OR-operation) of all bits of bytes 17 to 20
(Warning 1 to Warning 4).
0
In bytes 17 and 20, no warnings are active (all bits are set to 0).
1
Collective signal 03:
Contains the result of a disjunction (OR-operation) of all bits of bytes 15 and 16 (Fault
1 and Fault 2).
The actuator cannot be operated.
0
In bytes 15 and 16, no faults are active (all bits are set to 0).
1
Collective signal 09:
Indication according to NAMUR recommendation NE 107
Recommendation to perform maintenance.
Contains the result of a disjunction (OR-operation) of all bits of byte 24 (Maintenance
required).
0
In all bits of byte 24, no signals are active (all bits are set to 0).
1
Collective signal 07:
Indication according to NAMUR recommendation NE 107
Actuator is operated outside the normal operation conditions.
Contains the result of a disjunction (OR-operation) of all bits of bytes 25 to 28 (Out
of specification 1 to 4).
0
In bytes 25 and 28, no signals are active (all bits are set to 0).
1
Collective signal 08:
Indication according to NAMUR recommendation NE 107
The actuator is being worked on; output signals are temporarily invalid.
Contains the result of a disjunction (OR-operation) of all bits of bytes 29 and 30
(Function check 1 and 2).
0
In bytes 29 and 30, no signals are active (all bits are set to 0).
1
Collective signal 10:
Indication according to NAMUR recommendation NE 107
Actuator function failure, output signals are invalid.
Contains the result of a disjunction (OR-operation) of all bits of byte 23 (Failure).
0
In all bits of byte 23, no signals are active (all bits are set to 0).
1
Collective signal 05:
The device is ready for remote control.
No AUMA warnings, AUMA faults or signals according to NAMUR are present.
Bit 7 is set if bits 0 to 6 are deleted.
0
Contains the result of a disjunction (OR-operation) of bits 0 to 6 (device status).
AC 01.2/ACExC 01.2 Modbus RTU