Description Of The Output Data; Byte 1: Commands - AUMA AUMATIC AC 01.2 Manual

Hide thumbs Also See for AUMATIC AC 01.2:
Table of Contents

Advertisement

Actuator controls
AC 01.2/ACExC 01.2 Modbus RTU
Offset (hexadecimal)
Offset (decimal)
0x03E8
1000
0x03E9
1001
0x03EA
1002
0x03EB
1003
0x03EC
1004
0x03ED
1005
0x03EE
1006
0x03EF
0x03F4
1007
4.2.2.

Description of the output data

Register contents
Byte 3: setpoint position /(process setpoint, option) High byte
Byte 4: setpoint position /(process setpoint), option Low byte
Byte 9: Actual process value (high byte)
Byte 10: Actual process value (low byte)
Byte 11 Output AOUT 1 (high byte)
Byte 12: Output AOUT 1 (Low-Byte)
Byte 13 Output AOUT 2 (high byte)
Byte 14: Output AOUT 2 (low byte)
1012
Byte 15 to byte 26: Reserve

Byte 1: Commands

Table 24: Byte 1: Commands
Bit
Designation
(process representation)
0
Fieldbus OPEN
1
Fieldbus CLOSE
Description of the data interface
Value
Description
1
Operation command in direction OPEN
0
No command
1
Operation command in direction CLOSE
0
No command
option
option
29

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aumatic acexc 01.2

Table of Contents