Byte 18: Warnings 2; Byte 19: Warnings 3 - AUMA AUMATIC AC 01.2 Manual

Hide thumbs Also See for AUMATIC AC 01.2:
Table of Contents

Advertisement

Actuator controls
AC 01.2/ACExC 01.2 Modbus RTU
1)
The safety function indications via fieldbus are for information only and must not be used as part of a safety function. The I/O signals of
the SIL module must be used for this purpose.
Table 12: Byte 18: Warnings 2
Bit
Designation
(process representation)
0
Bit: Wrn controls temp
1
2
3
Bit: 24 V DC, external
4
5
Bit: RTC button cell
6
Bit: RTC not set
7
Bit: Config. warning
Table 13: Byte 19: Warnings 3
Bit
Designation
(process representation)
0
Bit: Wrn FOC budget
1
Bit: Wrn FO cables
2
Bit: Wrn input AIN 2
3
Bit: Wrn input AIN 1
4
Bit: Internal warning
5
Bit: WrnOnTiStarts
6
Bit: WrnOnTiRunning
7
Bit: Op. time warning

Byte 18: Warnings 2

Value
Description
1
Warning: Temperature within controls housing too high
0
No signal
No signal (reserved)
No signal (reserved)
1
The external 24 V AC voltage supply of the controls has exceeded the power supply
limits.
0
No signal
No signal (reserved)
1
Warning: The voltage of the RTC button cell is too low.
0
No signal
1
The real time clock has not yet been set on the basis of valid values.
0
No signal
1
Warning: Configuration setting is incorrect.
The device can still be operated with restrictions.
0
No signal

Byte 19: Warnings 3

Value
Description
1
Warning: FO cable system reserve reached (critical or permissible Rx receive level)
0
No signal
1
Warning:
Optical receiving signal (channel 1) incorrect (no or insufficient Rx receive level) or
RS-485 format error (incorrect bit(s))
0
No signal
1
Warning: Loss of signal analogue input 2
0
No signal
1
Warning: Loss of signal analogue input 1
0
No signal
1
Collective signal 15: Internal warning
0
No internal warning
1
Warning: Max. number of motor starts (starts) exceeded
0
No signal
1
Warning: Max. running time/h exceeded
0
No signal
1
Warning: Max. permissible operating time for an operation (OPEN-CLOSE) exceeded
0
No signal
Description of the data interface
19

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aumatic acexc 01.2