Actuator controls
AC 01.2/ACExC 01.2 Modbus RTU
Bit
Designation
(process representation)
2
Bit: Interlock active
3
Bit: Local STOP
4
Bit: EMCY stop active
5
Bit: EMCY behav. act.
6
Bit: FailState fieldbus
7
Bit: I/O interface
Table 8: Byte 14: Not ready REMOTE 2
Bit
Designation
(process representation)
0
1
2
Bit: SIL function active
3
Bit: Disabled
4
Bit: Interlock by-pass
5
Bit: PVST active
6
Bit: Service active
7
Bit: Handwheel active
1)
The safety function indications via fieldbus are for information only and must not be used as part of a safety function. The I/O signals of
the SIL module must be used for this purpose.
Table 9: Byte 15: Fault 1
Bit
Designation
(process representation)
0
Bit: Configuration error
1
Bit: Mains quality
2
Bit: Thermal fault
Value
Description
1
Actuator is interlocked.
0
No signal
1
Push button STOP of local controls is operated.
0
No signal
1
Operation mode EMERGENCY stop is active (EMERGENCY stop button has been
pressed).
0
EMERGENCY stop button not pressed (normal operation).
1
Operation mode EMERGENCY behaviour is active (EMERGENCY signal was sent).
0
No signal
1
No valid communication via fieldbus (despite available connection)
0
Communication via fieldbus is ok.
1
The actuator is controlled via the I/O interface (parallel).
0
The actuator is controlled via fieldbus.

Byte 14: Not ready REMOTE 2

Value
Description
No signal (reserved)
No signal (reserved)
1)
1
The safety function of the SIL sub-assembly is active.
0
No signal.
1
Actuator is in operation mode Disabled..
0
No signal
1
By-pass of Interlock function is active.
0
No signal
1
Partial Valve Stroke Test (PVST) is active.
0
No signal
1
Operation mode Service is active.
0
No signal
1
Manual operation is active (handwheel is engaged); optional indication
0
No signal

Byte 15: Fault 1

The fault signals contain the causes why the actuator cannot be operated.
Value
Description
1
Incorrect configuration, i.e. the current setting of the actuator controls is invalid.
0
Configuration is ok.
1
Due to insufficient mains quality, the controls cannot detect the phase sequence
(sequence of phase conductors L1, L2 and L3) within the pre-set time frame provided
for monitoring.
0
No signal
1
Motor protection tripped
0
No signal
Description of the data interface