AC 01.2/ACExC 01.2 Modbus RTU
Table 1: Byte 1: Logical signals
Bit
Designation
(process representation)
0
Bit: End p. OPEN
1
Bit: End p. CLOSED
2
Bit: Setpoint reached
3
Bit: Not ready REMOTE
4
Bit: Running OPEN
5
Bit: Running CLOSE
6
Bit: Warnings
7
Bit: Fault
Table 2: Byte 2: Actuator signals
Bit
Designation
(process representation)
0
Bit: Thermal fault
1
Bit: Phase failure
2
Bit: Sel. sw. REMOTE
3
Bit: Sel. sw. LOCAL
4
Bit: Limit sw. OPEN
5
Bit: Limit sw. CLOSED
Value
Description
1
For limit seating: Limit switch operated in direction OPEN
For torque seating: Torque switch and limit switch operated in direction OPEN
0
No signal
1
For limit seating: Limit switch operated in direction CLOSE
For torque seating: Torque switch and limit switch operated in direction CLOSE
0
No signal
1
The setpoint is within max. error variable (outer dead band). Is only signalled if
Modbus master has set the Fieldbus SETPOINT bit (process representation output).
0
No signal
1
Collective signal 04:
Contains the result of a disjunction (OR-operation) of all bits comprised in bytes 13
and 14 (Not ready REMOTE 1 and Not ready REMOTE 2).
The actuator cannot be operated from REMOTE.
The actuator can only be operated via the local controls.
0
In bytes 13 and 14, no signals are active (all bits are set to 0).
1
An operation command in direction OPEN is performed via fieldbus: Fieldbus OPEN
or Fieldbus SETPOINT (process representation output). This bit remains also set
during operation pauses (e.g. due to the dead time or the reversing prevention time).
0
Operation in direction OPEN via fieldbus is not executed.
1
An operation command in direction CLOSE is performed via fieldbus: Fieldbus CLOSE
or Fieldbus SETPOINT (process representation output). This bit remains also set
during operation pauses (e.g. due to the dead time or the reversing prevention time).
0
Operation in direction CLOSE via fieldbus is not executed.
1
Collective signal 02:
Contains the result of a disjunction (OR-operation) of all bits of bytes 17 to 20
(Warning 1 to Warning 4).
0
In bytes 17 and 20, no warnings are active (all bits are set to 0).
1
Collective signal 03:
Contains the result of a disjunction (OR-operation) of all bits of bytes 15 and 16 (Fault
1 and Fault 2).
The actuator cannot be operated.
0
In bytes 15 and 16, no faults are active (all bits are set to 0).
Byte 2: Actuator signals
Value
Description
1
Motor protection tripped
0
No signal
1
When connecting to a 3-ph AC system and with internal 24 V DC supply of the
electronics: Phase 2 is missing.
When connecting to a 3-ph or 1-ph AC system and with external 24 V DC supply
of the electronics: One of the phases L1, L2 or L3 is missing.
0
All phases are available.
1
Selector switch is in position REMOTE.
0
Selector switch is not in position REMOTE.
1
Selector switch is in position LOCAL.
0
Selector switch is not in position LOCAL.
1
Limit switch operated in direction OPEN
0
No signal
1
Limit switch operated in direction CLOSE
0
No signal