Application functions
Tx active channel
Tx both channels
12.3.
Intermediate positions
Conditions
Characteristics
12.3.1.
Define the pivot points of intermediate positions
Information
12.3.2.
Set signal behaviour of intermediate positions
No signal
C________|¯¯¯¯¯¯¯¯O
C¯¯¯¯¯¯¯¯¯|_______O
C_______|¯|_______O
56
Setting values:
Response telegrams are only sent via the active channel.
Response telegrams are sent via both channels, the active and the passive channel.
The actuator is equipped with a position transmitter.
With the integral controls, up to 8 intermediate positions can be set to any value
between 0 % and 100 % of the travel.
Each intermediate position can be activated or deactivated individually.
When reaching an intermediate position, a signal can be generated.
A hysteresis can be defined for each pivot point.
Each intermediate position can be set to a value between 0 and 100 % of the travel.
Customer settings M0041
Intermediate positions M0143
Pivot points M0160
Pivot point 1 M0249
Default values: 0.0 % for all 8 intermediate positions
Setting range: 0.0 % (CLOSED) to 100.0 % (OPEN) of the travel
The pivot points also apply to the <Operation profile> function.
Reaching a pivot point (intermediate position) can be signalled:
via fieldbus (refer to separate operation instructions)
via indication lights (LEDs) of the local controls or
via output contacts
Each pivot point (intermediate position) can be assigned a specific signal behaviour.
Customer settings M0041
Intermediate positions M0143
Signal behaviour M0266
Signal behaviour 1 M0269
Default value: No signal
Setting values:
Behaviour A: "Off", intermediate position is not signalled.
Behaviour B: Signal is active from reaching the pivot point (P) up to end position
OPEN (100 %)
Behaviour C: Signal is active from end position CLOSED (0 %) until reaching the
pivot point (P).
Behaviour D: When passing the pivot point (P), a pulse signal is issued.
Multi-turn actuators
TR-M30X
TR-M1000X