Actuator controls
AC 01.2/ACExC 01.2 Modbus RTU
No.
Type
Parameter
67-7
U16
Reset time Ti
67-8
U16
Rate time Td
67-9
U16
Min reaction act. value
67-10
U16
Max reaction act. value
67-11
U16
React. time act. value
67-12
enum
Actual value source
67-13
enum
Modulating behaviour
Table 46: Failure behaviour
No.
Type
Parameter
Offset (hexadecimal) = 0x04BF
Offset (decimal) = 1215
Data length = 12 bytes
15-1
enum

Failure behaviour

15-2
enum
Failure operation
15-3
enum
Failure source
15-4
Mmss01
Delay time
15-5
U16
Failure position
15-6
U16
Failure position MPV
Table 47: EMERGENCY behaviour
No.
Type
Parameter
Offset (hexadecimal) = 0x04C0
Offset (decimal) = 1216
Data length = 26 bytes
16-1
enum
Failure reaction EMCY
16-2
enum
EMCY operation mode
Access
Default
Setting value
R/W
1000
Min = 1 [s]
Max = 1000 [s]
R/W
0
Min = 0 [s]
Max = 100 [s]
R/W
0
Min = 0 [0.1 %]
Min = 100 [0.1 %]
R/W
1000
Min = 100 [0.1 %]
Max = 1000 [0.1 %]
R/W
0
Min = 0 [s]
Max = 100 [s]
R/W
0
0 : I/O interface
1 : Fieldbus interface
R/W
0
0: P controller
1: PI controller
2: PID controller
Access
Default
Setting value
R/W
1
0 : Good signal first
1 : Immediately active
R/W
0
0 : STOP
1 : CLOSE
2 : OPEN
3 : Approach position
4 : Execute last CMD
R/W
4
1 : Fieldbus interface
2 : I/O interface
4 : Active interface
R/W
30
Min = 0 [0,1 s]
Max = 1800 [0,1 s]
R/W
500
Min = 0 [0.1 %]
Max = 1000 [0.1 %]
R/W
500
Min = 0 [0.1 %]
Max = 1000 [0.1 %]
Access
Default
Setting value
R/W
1
1 : Good signal first
2 : Immediately active
R/W
0
0 : Remote only
1 : Remote and local
Appendix
Explanation
Reset time Ti
Rate time Td
Minimum reaction required of
actual process value within reac-
tion time
Maximum reaction required of
actual process value within reac-
tion time
Reaction time for monitoring
min. or max. reaction of actual
process value
Actual value source of process
controller
Modulating behaviour of PID
controller
Explanation
Activate failure behaviour
Setting the actuator reaction for
active failure behaviour
Failure source (failure reason)
for failure behaviour
Failure operation is only ex-
ecuted after delay time has ex-
pired.
Failure position in percent
Failure position of multiport
valve
Explanation
Failure reaction EMERGENCY.
The EMERGENCY failure reac-
tion defines the actuator beha-
viour once the EMERGENCY
signal is initiated.
Determines the availability of
EMERGENCY behaviour de-
pending on the selector switch
position Local or Remote
55