Description of the data interface
Bit
Designation
(process representation)
6
Bit: RTC not set
7
Bit: Config. warning
Table 19: Byte 27: Out of specification 3
Bit
Designation
(process representation)
0
Bit: Wrn FOC budget
1
Bit: Wrn FO cables
2
Bit: Wrn input AIN 2
3
Bit: Wrn input AIN 1
4
Bit: Internal warning
5
Bit: WrnOnTiStarts
6
Bit: WrnOnTiRunning
7
Bit: Op. time warning
Table 20: Byte 28: Out of specification 4
Bit
Designation
(process representation)
0
1
2
Bit: WrnSetpointPos
3
Bit: PVST required
4
Bit: Wrn FOC connection
5
Bit: Failure behav. act.
6
Bit: PVST abort
7
Bit: PVST error
22
Value
Description
1
The real time clock has not yet been set on the basis of valid values.
0
No signal
1
Warning: Configuration setting is incorrect.
The device can still be operated with restrictions.
0
No signal

Byte 27: Out of specification 3

Value
Description
1
Warning: FO cable system reserve reached (critical or permissible Rx receive level)
0
No signal
1
Warning:
Optical receiving signal (channel 1) incorrect (no or insufficient Rx receive level) or
RS-485 format error (incorrect bit(s))
0
No signal
1
Warning: Loss of signal analogue input 2
0
No signal
1
Warning: Loss of signal analogue input 1
0
No signal
1
Collective signal 15: Internal warning
0
No internal warning
1
Warning: Max. number of motor starts (starts) exceeded
0
No signal
1
Warning: Max. running time/h exceeded
0
No signal
1
Warning: Max. permissible operating time for an operation (OPEN-CLOSE) exceeded
0
No signal

Byte 28: Out of specification 4

Value
Description
No signal (reserved)
No signal (reserved)
1
Warning: Loss of signal of actuator setpoint position
0
No signal
1
Warning: A Partial Valve Stroke Test (PVST) should be performed.
0
No signal
1
Warning: FO cable connection not available.
0
No signal
1
The failure behaviour is active.
0
No signal
1
Partial Valve Stroke Test (PVST) was aborted or could not be started. Remedy:
Perform RESET or restart PVST.
0
No signal
1
Partial Valve Stroke Test (PVST) could not be successfully completed.
0
No signal
Actuator controls
AC 01.2/ACExC 01.2 Modbus RTU