Interface To Service Devices; Diagnosis Levels - Siemens FDM223 Technical Manual

Manual call point
Hide thumbs Also See for FDM223:
Table of Contents

Advertisement

Structure and function
3
Function

3.3.5 Interface to service devices

3.3.6 Diagnosis levels

Information displayed on
the detector exchanger
and tester
'No deviation'
1
'needed excha.' 
2
Other fault message 
20 | 54
A proximity interface (MC link) is available for commissioning and maintenance in
order to communicate with the detector exchanger and tester FDUD292 and the
intelligent detector tester FDUD293.
You will find additional information in documents 007227 and 009718.
See also
2
Applicable documents [➙ 7]
The manual call point monitors its operation largely autonomously.
The following diagnosis levels are derived from the different control measurements:
Normal
Replacement necessary
Fault
For details, see table below.
When an error occurs which impairs the correct functionality of the device, a fault
message is reported to the control panel.
To remedy the cause, additional information is available in the manual call point.
This can be displayed by the detector exchanger and tester FDUD292 or the
intelligent detector tester FDUD293, for example.
You will find additional information in documents 007227 and 009718.
Meaning
Normal, no fault is present
The manual call point is fully functional
Replacement necessary
Key monitoring outside the tolerance
range
Fault present
Alarming no longer guaranteed
Key monitoring outside the
tolerance range or malfunctioning
due to external influences
Supply error
Software error (Watchdog error)
Memory error
Communication error between the
manual call point and the control panel
1
The information displayed on the detector exchanger and tester is always in
English; no translation into the corresponding language.
2
This status can be displayed together with other statuses, e.g. 'needed
excha.' (replacement necessary).
See also
2
Applicable documents [➙ 7]
Measures
None
Replace manual call point
Replace manual call point
Check detector line voltage
Replace manual call point
Replace manual call point
Replace manual call point
Remedy cause
007002_k_en_--