Section 3
3.4.4 SINGLE MOUNTING TRACK ASSEMBLY/TRANSDUCER INSTALLATION FOR
SINGLE CHANNEL INTEGRATED 1020 FLOWMETER
Connect power cables to flowmeter as required (see drawing 1020-7).
Apply power to flowmeter.
Perform all required Installation Menu steps until the flowmeter issues the Number Index. Record
the number index value displayed in the [Pick/Install Xdcr] menu. This number index value will be
used to position the transducer.
Number
Index
Current Menu
Selection
Locate positions on pipe for transducer Single Mounting Track Assembly (see paragraph 3.3.2).
Place mounting straps around the pipe and the Mounting Track Assembly (Figure 1).
Mounting Strap
Tighten the mounting strap screws enough to take up all of the slack, but not enough to prevent
rotation of the assembly. Rotate the assembly on the pipe to the 9 o'clock position ensuring that
it is a smooth area without any raised spots or seams. Mark a generous area around the mounting
frame (1/2" on either side and half again the length front and back) with a pencil or chalk (Figure
2). Move or revolve the assembly away from the area marked (loosen straps if necessary to do
this).
Figure 1
Strap Screw
Number index 25
>Pick/Install Xdcr
3-16
1020NFM-1D
W ide B eam
Wide Beam
C lamp-O n
Clamp-On
Ultrasonic
U ltrasonic
Flowmeter
Flow meter
Figure 2