4.4 Start-Up Flowcharts
 Subchart A-3: Operation with Permanent Magnet Motors
Flowchart A-3 in
Figure 4.11
motors can be used for more energy-efficient operation in reduced or variable torque applications.
Note: 1. Although the drive sets parameters for the PG encoder during Auto-Tuning, sometimes the direction of the motor and direction of the
PG get reversed. Use parameter F1-05 to switch the direction of the PG so that it matches the motor direction.
2. The Z pulse must be realigned if the PG encoder is replaced. Set T2-01 to 3 to recalibrate the drive for the new encoder.
Figure 4.10
<1> A motor code can be entered as the parameter setting for E5-01 when using a Yaskawa PM motor (SMRA Series, SSR1 Series, and SST4
Series). If using a motor from another manufacturer, enter FFFF.
<2> Make sure the motor and load can run freely, i.e., if a brake is mounted, make sure it is released.
<3> ASR Gain Tuning automatically performs Inertia Tuning and sets parameters related to Feed Forward function.
108
describes the set-up procedure for running a PM motor in Open Loop Vector Control. PM
From
Flowchart
A
NO
Motor test report/
data sheet available?
YES
Input the motor data.
<1>
(T2-01 = 0)
Run the motor without load; check the rotation direction and operation.
Verify external signal commands to the drive work as desired.
NO
NO
replaced after Auto-Tuning was
Disconnect the motor from the load so that the motor shaft can rotate.
Perform Z Pulse Offset Tuning.
Connect the load to the motor.
NO
Perform PM Inertia Tuning.
Run the machine and check for
desired operation.
Return to
Flowchart
A
Figure 4.11 Operation with Permanent Magnet Motors
Possible
YES
for motor to rotate
during tuning?
NO
Input the motor data.
<1>
(T2-01 = 1)
YES
Is the motor cable longer
than 50 meters?
PM Stationary Auto-Tuning for
Stator Resistance (T2-01 = 2)
NO
Is there a
PG encoder on the
motor?
YES
Has PG been
performed?
YES
Is reverse
operation disabled?
(b1-04 = 1)
YES
Enable reverse operation.
(b1-04 = 0)
(T2-01 = 3)
Should the drive set ASR?
NO
Does the application
require Feed Forward
function?
YES
Perform ASR gain tuning.
<2>
(T2-01=8)
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
Perform PM
Rotational Auto-Tuning.
(T2-01 = 14)
common_TMo
nly
NO
YES
<3>
(T2-01=9)