Subchart A-2: High Performance Operation Using Olv Or Clv - YASKAWA U1000 Series Technical Manual

Rated output current: 200 v class: 22 to 248 a, 400 v class: 9.6 to 414 a
Hide thumbs Also See for U1000 Series:
Table of Contents

Advertisement

 Subchart A-2: High Performance Operation Using OLV or CLV
Flowchart A-2 in
Figure 4.10
Closed Loop Vector Control. Appropriate for applications requiring high starting torque and torque limits.
Note: Although the drive sets parameters for the PG encoder during Auto-Tuning, sometimes the direction of the motor and direction
of the PG get reversed. Use parameter F1-05 to switch the direction of the PG so that it matches the motor direction.
Figure 4.9
Perform Stationary
Auto-Tuning 3 (T1-01 = 5)
<1> The load must be decoupled from the motor to properly perform Rotational Auto-Tuning.
<2> Rotational Auto-Tuning can still be performed if the load is 30% or less, though Stationary Auto-Tuning will probably yield better control
performance.
<3> Run the operation in test mode for Auto-Tuning 3. The drive will automatically set motor parameters automatically. For details, refer to
Stationary Auto-Tuning 3 on page
<4> Make sure the motor and load can run freely, i.e., if a brake is mounted, make sure it is released.
<5> ASR Gain Tuning automatically performs Inertia Tuning and sets parameters related to Feed Forward function.
Figure 4.10 Flowchart A-2: High Performance Operation Using OLV or CLV
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
describes the setup procedure for high-performance with Open Loop Vector Control or
From
Flowchart
A
Possible for motor to
<1>
rotate during tuning?
NO
Motor test report/
data sheet available?
NO
YES
Is the load less than
30% of the rated load
for the motor?
NO
Obtain a test report from the motor manufacturer
<3>
and perform Stationary Auto-Tuning 2 (T1-01 = 4).
Run the motor without load; check the rotation direction and operation.
Verify external signal commands to the drive work as desired.
Run the operation in test mode for Auto-Tuning 3.
Connect the load to the motor.
Is there a PG
encoder on the
motor?
YES
Should the
drive set ASR gain
automatically?
NO
Does the application
require Feed Forward
function?
NO
Run the machine and check for desired
operation.
Return to
Flowchart
A
120.
YES
YES
Perform Stationary
Auto-Tuning 2 (T1-01 = 4)
NO
YES
YES
Perform Inertia Tuning
<4>
(T1-01 = 8)
4.4 Start-Up Flowcharts
<2>
Perform Rotating
Auto-Tuning (T1-01 = 0)
common_TMo
nly
Perform ASR gain tuning.
<5>
(T1-01 = 9)
4
107