YASKAWA U1000 Series Technical Manual page 438

Rated output current: 200 v class: 22 to 248 a, 400 v class: 9.6 to 414 a
Hide thumbs Also See for U1000 Series:
Table of Contents

Advertisement

B.3 Parameter Table
H2-
Function
Setting
3F
PID Feedback High
4C
During Fast Stop
4D
oH Pre-alarm Time Limit
60
Internal Cooling Fan Alarm
61
Rotor Position Detection Complete
Memobus Regs1 (It selects it with
62
H2-07 and H2-08.)
Memobus Regs2 (It selects it with
63
H2-09 and H2-10.)
64
During Commercial Power Operation
90 to 92
DriveWorksEZ Digital Outputs 1 to 3
100 to 192
Function 0 to 92 with Inverse Output
H3: Multi-Function Analog Inputs
No.(Addr.)
Name
H3-01
Terminal A1 Signal Level
(410H)
Selection
H3-02
Terminal A1 Function Selection
(434H)
H3-03
(411H)
Terminal A1 Gain Setting
H3-04
(412H)
Terminal A1 Bias Setting
H3-05
Terminal A3 Signal Level
(413H)
Selection
H3-06
Terminal A3 Function Selection
(414H)
H3-07
(415H)
Terminal A3 Gain Setting
H3-08
(416H)
Terminal A3 Bias Setting
H3-09
Terminal A2 Signal Level
(417H)
Selection
438
H2 Multi-Function Digital Output Settings
All Modes
Closed: The PID feedback level is too high.
All Modes
Closed: A Fast Stop command has been entered from the operator or input terminals.
All Modes
Closed: oH pre-alarm time limit has passed.
All Modes
Closed: Internal cooling fan alarm
V/f
V/f w/PG
OLV/PM
AOLV/PM
Closed: Drive has successfully detected the rotor position of the PM motor.
All Modes
The contact output is closed if any of the bits that are specified by H2-08 for the MEMOBUS/Modbus register address
that is set in H2-07 turns on.
All Modes
The contact output is closed if any of the bits that are specified by H2-10 for the MEMOBUS/Modbus register address
that is set in H2-09 turns on.
V/f
V/f w/PG
OLV/PM
AOLV/PM
Closed: Operating on commercial power.
All Modes
Reserved for DWEZ digital output functions.
All Modes
Inverts the output switching of the multi-function output functions.
Set the last two digits of 1 to reverse the output signal of that specific function.
All Modes
0: 0 to 10 V
1: -10 to 10 V
All Modes
Sets the function of terminal A1.
All Modes
Sets the level of the input value selected in H3-02 when 10 V is input at terminal A1.
All Modes
Sets the level of the input value selected in H3-02 when 0 V is input at terminal A1.
All Modes
0: 0 to 10 V
1: -10 to 10 V
All Modes
Sets the function of terminal A3.
All Modes
Sets the level of the input value selected in H3-06 when 10 V is input at terminal A3.
All Modes
Sets the level of the input value selected in H3-06 when 0 V is input at terminal A3.
All Modes
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
3: 0 to 20 mA
Note: Use DIP switch S1 to set input terminal A2 for a current or a voltage input signal.
Description
OLV
CLV
CLV/PM
OLV
CLV
CLV/PM
Description
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
common_
TMonly
common_
TMonly
common_
TMonly
common_
TMonly
common_
TMonly
common_
TMonly
common_
TMonly
common_
TMonly
common_
TMonly
common_
TMonly
Setting
common_
Default: 0
TMonly
Min: 0
Max: 1
Default: 0
common_
TMonly
Min: 0
Max: 32
Default: 100.0%
common_
TMonly
Min: -999.9%
Max: 999.9%
Default: 0.0%
common_
TMonly
Min: -999.9%
Max: 999.9%
common_
Default: 0
TMonly
Min: 0
Max: 1
Default: 2
common_
TMonly
Min: 0
Max: 32
Default: 100.0%
common_
TMonly
Min: -999.9%
Max: 999.9%
Default: 0.0%
common_
TMonly
Min: -999.9%
Max: 999.9%
common_
TMonly
Default: 2
Min: 0
Max: 3
Page
245
245
245
245
245
246
246
246
246
246
Page
247
247
247
247
248
248
248
248
248