C.7 Message Format - YASKAWA U1000 Series Technical Manual

Rated output current: 200 v class: 22 to 248 a, 400 v class: 9.6 to 414 a
Hide thumbs Also See for U1000 Series:
Table of Contents

Advertisement

C.7 Message Format

 Message Content
In MEMOBUS/Modbus communications, the master sends commands to the slave, and the slave responds. The message
format is configured for both sending and receiving as shown below, and the length of data packets depends on the
command (function) content.
 Slave Address
The slave address in the message defines the note the message is sent to. Use addresses between 0 and FF (hex). If a
message with slave address 0 is sent (broadcast), the command from the master will be received by all slaves. The slaves
do not provide a response to a broadcast type message.
 Function Code
The three types of function codes are shown in the table below.
Function
Code
03H
Read MEMOBUS/Modbus registers
08H
Loopback test
10H
Write to multiple MEMOBUS/Modbus registers
 Data
Configure consecutive data by combining the MEMOBUS/Modbus register address (test code in case of a loopback test)
and the data the register contains. The data length changes depending on the command details.
A drive MEMOBUS/Modbus register always has a data length of two bytes. Therefore data written into drive registers
must also always have a length of two bytes. Register data read out from the drive will always consist of two bytes.
YASKAWA ELECTRIC SIEP C710636 03A YASKAWA U1000 Technical Manual
SLAVE ADDRESS
FUNCTION CODE
DATA
ERROR CHECK
Function Name
C.7 Message Format
common_
TMonly
Data Length (bytes)
Command Message
Minimum
Maximum
Minimum
8
8
8
8
11
41
Response Message
Maximum
7
37
8
8
8
8
C
497

Advertisement

Table of Contents
loading

Table of Contents